Control Panels Specifications | en 161
Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996
3 + AUX POWER Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on current
4 BATTERY - Bosch supplied wire lead, included with control panel.
5 BATTERY +
6 Output A (1) Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on current
7 Output B (2)
8 Output C (3)
9 COMMON
10 EARTH GROUND 16 AWG to 14 AWG (1.5 mm to 1.8 mm)
11 POINT 1 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω
12 POINT 1/2 COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω
13 POINT 2 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω
14 POINT 3 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω
15 POINT 3/4 COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω
16 POINT 4 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω
17 POINT 5 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω
18 POINT 5/6 COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω
19 POINT 6 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω
20 POINT 7 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to
1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω