Servicing and spares
Bosch Condens 5000W – 6 720 646 195 (2018/10)
38
After measurement replace test point cover.
The pressure will read negative, refer to the chart in figure 68.
Fig. 68 Fan pressure readings
If the boiler fails the fan pressure test then before adjusting the air/gas
ratio, try the following:
Check the syphon is not blocked.
1. Remove the screws securing the sump cover.
2. Remove the sump cover.
3. Clean the sump and heat exchanger with a suitable brush
Fig. 69 Sump access
Check the exhaust path and flue for restriction.
Clean the heat exchanger with a suitable cleaning tool. refer to
section 6.7 "Checking the heat exchanger".
Re-check the fan pressure readings
6.5 Flue gas analysis
Combustion test:
Connect the flue gas analyser to the flue gas sampling point as shown
in the figure 70.
Run the boiler at maximum output for at least 10 minutes.
Check the CO/CO
2
readings against the information in table 18 CO/
CO
2
settings.
Fig. 70 Combustion test
[1] Air inlet sample point
[2] Flue gas sample point
If the boiler fails the combustion test, check:
Air intake for restriction.
Diaphragm in the fan, for correct operation.
Cleanliness of the heat cell, plus blockages in the condensate
disposal.
NG Boiler
FAN PRESSURE TEST
Clean Heat Ex.
Heat Ex. ok
LPG Boiler
ZSB18-2A-23:
- 0.8
0
-0.6
-0.5
-0.4
-0.3
-0.2-0.1
-0.8
-0.7
kPa
ZSB18-2A-31:
- 0.74
0
-0.6
-0.5
-0.4
-0.3
-0.2-0.1
-0.8
-0.7
kPa
6720646195-13.1Wo
1.
1.
6720644743-24.1Wo
2.
3.
6720646195-12.1Wo
1
2