8 | Information for heating contractor
6720830560 (2015/06)CR10
4.5 Settings in the service menu
▶ A.1 = Set and confirm SC (zone controller).
-or-
▶ A.1 = Set and confirm Fb (remote control)
▶ Select and confirm heating circuit (HC = 1...8).
Setting Adjustment range
1)
Description
A.1 CO | Fb | SC Controller (CO), remote control (Fb), zone
controller (SC)
HC HC1 | HC2 | ... | HC7 |
HC8
Heating circuit/heating zone 1 to 8
2)
d.1 2 | 3 | 4 Control characteristics (reaction speed)
2: 2K P range = Quick reaction
3: 3K P range = Medium reaction
4: 4K P range = Slow reaction
E.1 – 3.0 ... 0.0 ... 3.0 Correction value for the room temperature
displayed
P.1 4 | 5 Flow temperature control (4) or output
control (5)
L 1 1 | 0 Optimised running of the pump: in the case
of flow temperature control, the heating
pump runs as briefly as possible.
Switching-off if there is a buffer cylinder in
the system.
C.1 C | F Unit of displayed temperatures °C (C) or °F
(F)