D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 18.0 Installer Menu
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 128
18.1.15 [7] Points Menu Parameters
Point indexes determine how points operate, and a point’s source gives a description as to the
physical location of the point for installation and service personnel. In this menu, you can get program
point indexes and sources.
Point Type Selections
24-Hour O/C Point
Part On Fire Point
Interior Aux AC Supervision
Interior Follower Gas Point
Keyswitch Maintained Custom Function
Keyswitch Momentary Keypad
Point Response Selections* 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open I I I I D D I I D I I I I I T
Short I I I I I I D D D I I I I I I
Disarmed Open T T T I I T I T
Short T T T I T I I
24-Hour Open I T I T I T S T S S Not Applicable
Short I I T T I T T S S S
*Selections: D = Delayed Response, I = Instant Alarm, S = Supervisory, T = Trouble, Blank = No Response
Point Index Description
Point Index Description Defaults:
1 24-hr Instant Open/Short
2 24-hr Inv/Sil on Short
3 Pull Station
4 Smoke Detector
5 Smoke Detector w/ Verification
6 Bell Supervision - D192G
7 Part On: Instant N/O
8 Perimeter: Delay N/O