EasyManua.ls Logo

Bosch D7412GV4 - B92 x;B91 x Users Menu; Change Passcode

Bosch D7412GV4
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | Appendix B: Point Address Charts
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 168
B.2 SDI2 Points
Not all off-board points supported by the control panel can be supported on B208 Octo-input
modules. Points 9 and 10, 19 and 20, etc. can be supported by ZONEX bus or SDI2 Wireless points.
Table 51: SDI2 Points
Octo-input Module
Rotary Switch Setting
Supported Points
0 Disabled
1 11 - 18
2 21 - 28
3 31 - 38
4 41 - 48
5 51 - 58
6 61 - 68
7 71 - 78
2
8 81 - 88
9 91 - 98
10 101 - 108
11 111 - 118
12 121 128
1
13 131 - 138
14 141 - 148
15 151 - 158
16 161 - 168
17 171 - 178
18 181 - 188
19 191 - 198
20 201 - 208
21 211 - 218
22 221 - 228
23 231 - 238
24 241 - 248
1
1
The D9412GV4 supports points 1 to 247 and modules 1-
24. Terminate point 128/248 with an EOL resistor.
2
The D7412GV4 supports points 1 to 75 and modules 1
- 7. Terminate points 76, 77, and 78 with EOL resistors.

Table of Contents

Other manuals for Bosch D7412GV4

Related product manuals