D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 12.0 SDI Devices
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 71
The ITS-DX4020-G GPRS/GSM IP
Communicator has two modes; GPRS uses
Modem4; and GSM uses Contact ID.
For programming information refer to the
ITS-DX4020-G GPRS/GSM IP Communicator
Installation and Operation Guide (P/N:
F01U163066
).
12.5.1 Address Settings
The DX4020 has specific DIP switch settings
for SDI Address 80. The B426, B420, and
DX4020 is capable of communication to
supported Automation packages, SDI
Addresses 88 and 92 when using the DX4020
for Remote Programming Software (RPS) or
enhanced communications in a local-area
network (LAN) or wide-area network (WAN)
environment. Refer to Figure 28 for the correct
switch settings.
12.5.2 Supervision
Supervision of Network Interface Modules at
SDI Addresses 88 and 92 are enabled
automatically when used to communicate with
a central station network receiver. Supervision
ensures reliable operation between the module
and the control panel.
If supervised and the module does not respond
to control panel supervision polls, then a
system fault message appears at the keypad.
The report to the receiver includes the address
of the troubled module indicating which
module needs service.
Figure 28: DX4020 DIP Switch Settings
1 - DIP Switches
2 - ON position
3 - OFF position
4 - SDI Address 80 switch settings
5 - SDI Address 88 switch settings
6 - SDI Address 92 switch settings