D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 18.0 Installer Menu
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 134
Point Index
B91x/B92x keypads Configuration of Point Index
1. Enter the installer passcode, and then open the [1] Installer menu.
2. Go to the [1] Program > [7] Points menu option. The keypad display toggles between
showing the point index and point source for the selected point.
3. Press [PREV] and [NEXT] to the desired point, or enter the point number.
4. Press [ENTER] to edit the point and then [ENTER] to edit the index for the selected point.
5. The [ESC] key acts as a [Backspace] button. Press [ESC] to delete the characters, and then
enter the new numbers.
6. Press [ENTER] to save the programming.
7. When the keypad shows Parameter Saved, escape from the menu.
B93x/B94x keypads Configuration of Point Index
1. Enter the installer passcode, and then open the [1] Installer menu.
2. Go to the [1] Program > [7] Points menu option. The keypad display toggles between
showing the point index and point source for the selected point.
3. Press [PREV]/ and [NEXT]/ to the desired point, or enter the point number.
4. Press the Edit softkey to change the index.
5. On the B93x, the [ESC] key acts as a [Backspace] button. The B94x has a [Backspace] key.
Delete the current characters, and then enter the new numbers.
6. Press the Save softkey.
7. When the keypad shows Parameter Saved, escape from the menu.
Point Source
B91x/B92x keypads Configuration of Point Source
1. Enter the installer passcode, and then open the [1] Installer menu.
2. Go to the [1] Program > [7] Points menu option. The keypad display toggles between
showing the point index and point source for the selected point.
3. Press [PREV] and [NEXT] to the desired source, or enter the point number.
4. Press [ENTER] to edit the point and then [NEXT] to go to the source option.
5. Press [ENTER] to edit the source for the selected point.
6. Use the [PREV] or [NEXT] buttons to scroll through the Not Assigned and Wireless options.
7. Press [ENTER] while viewing the desired source to save the programming.
8. When the keypad shows Parameter Saved, escape from the menu.
B93x/B94x keypads Configuration of Point Source
1. Enter the installer passcode, and then open the [1] Installer menu.
2. Go to the [1] Program > [7] Points menu option. The keypad shows the point index for the
selected point.
3. Press [PREV]/ and [NEXT]/ to the desired point, or enter the point number.
4. Press the Source softkey to view and edit the source, and then press the Edit softkey to edit
the source.
5. Use the [PREV]/ or [NEXT]/ buttons to scroll through the Not Assigned, Octo-input, Outo-
output, Zonex, Keypad, and Wireless options.
6. Press the Save softkey.
7. When the keypad shows Parameter Saved, escape from the menu.