20 POINT 7 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100
Ω
21 POINT 7/8
COMMON
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100
Ω
22 POINT 8 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100
Ω
23 ZONEX
COMMON
22 AWG min (up to 14 AWG max)
24 ZONEX POWER 22 AWG min (up to 14 AWG max)
25 ZONEX IN 2* 22 AWG min (up to 14 AWG max)
26 ZONEX OUT 2* 22 AWG min (up to 14 AWG max)
27 ZONEX IN 1 22 AWG min (up to 14 AWG max)
28 ZONEX OUT 1 22 AWG min (up to 14 AWG max)
29 SDI COMMON Terminal accommodates 14 to 22 AWG, use appropriate wire size based on
peripheral device current
30 SDI DATA
BUS B
22 AWG min (up to 14 AWG max)
31 SDI DATA
BUS A
22 AWG min (up to 14 AWG max)
32 SDI POWER Terminal accommodates 14 to 22 AWG, use appropriate wire size based on
peripheral device current
33 SDI2
COMMON
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on
peripheral device current
34 SDI2 DATA
BUS B
22 AWG min (up to 14 AWG max)
35 SDI2 DATA
BUS A
22 AWG min (up to 14 AWG max)
36 SDI2 POWER Terminal accommodates 14 to 22 AWG, use appropriate wire size based on
peripheral device current
*D9412GV4 only. Terminals 25 and 26 are NOT USED on the D7412GV4 Control Panel.