EasyManua.ls Logo

Bosch DS7400Xi - Max. Load Currents; Backup Battery Calculation; Standby Current Load

Bosch DS7400Xi
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 5
1.16 Backup Battery Calculation
The following table is used to calculate the standby battery
capacity required by NFPA when using the DS7400Xi:
1.17 Standby Current Load
Battery Ah - (20% Storage + 0.375 Ah Alarm)
The following table is the derated battery divided by hours minus the control standby (175 mA):
1.15 Max. Load Currents
* = Add 15 mA for each additional zone in alarm.
** = When calculating Standby and Alarm Current for the Octal Relay Module, use 10 mA plus 40 mA for each activated relay.
*** = Maximum current draw if using the DS7400Xi Panel power supply. Total of all outputs cannot exceed 750 mA.
Rechargeable
Battery Size
Max. Standby
for 4 hours
Max. Standby
for 8 hours
Max. Standby
for 24 hours
Max. Standby
for 48 hours
Max. Standby
for 60 hours
Max. Standby
for 72 hours
Max. Standby
for 80 hours
7 Ah 1.0 A 470 mA X X X X X
8 Ah 1.2 A 580 mA X X X X X
14 Ah 1.5 A 1.1 A 270 mA X X X X
15 Ah 1.5 A 1.2 A 300 mA X X X X
17.2 Ah 1.5 A 1.5 A 380 mA 100 mA X X X
21 Ah 1.5 A 1.5 A 500 mA 160 mA 100 mA X X
28 Ah 1.5 A 1.5 A 740 mA 280 mA 190 mA 130 mA 100 mA
30 Ah 1.5 A 1.5 A 800 mA 310 mA 210 mA 150 mA 120 mA
35 Ah 1.5 A 1.5 A 970 mA 400 mA 280 mA 200 mA 170 mA
Device
Quantity
Standby Current
per Device
Total Standby
Current
(Quantity x Standby
Current per Device)
Alarm Current
per Device
Total Alarm
Current
(Quantity x Alarm
Current per Device)
DS7400Xi (4+) Control Panel 1 175 mA 175 mA 250 mA 250 mA
DS7416i Advanced Radio Communications Module 127 mA 127 mA
DS7412 - RS232 Serial Interface Module 35 mA max. 35 mA max.
DS7420i -Dual Phone Line/Bell Supervision Module 20 mA 140 mA
DS7430 – Multiplex Expansion Module 65 mA 65 mA
DS7432 – 8-Input Remote Module 10 mA 10 mA
DS7433 – 8-Input Direct Module 65 mA 80 mA*
DS7436 – Dual Multiplex Expansion Module 130 mA 130 mA
DS7445/DS7445i Keypad 75 mA 75 mA
DS7447/ DS7447E Keypad 100 mA 100 mA
DS7448 Keypad 80 mA 100 mA
DS7450, DS7452, DS7455 Contact Points
350
μ
A
350
μ
A
DS7457 – Single Zone Multiplex Input Module
350
μ
A
350
μ
A
DS7460 – Dual Zone Module 1 mA 1 mA
DS7465 – Input/Output Module 1 mA 1 mA
DS7480 – Bell Supervision Module 7 mA 50 mA
DS7481 – Single Phone Line Monitor 20 mA 20 mA
DS7488 – Octal Relay Module** 10 mA + 40 mA** 10 mA + 40 mA**
DS7489 – Solid State Output Module 10 mA 750 mA max.***
MX280 Series Multiplex Smoke Detectors
500
μ
A
560
μ
A
MX540 (DS7473) PIR Detector
800
μ
A
800
μ
A
MX835 TriTech
®
PIR/Microwave Detector 6 mA 35 mA
MX775 (DS7470) PIR Detector
200
μ
A
200
μ
A
MX794 (DS7474) PIR Detector
800
μ
A
800
μ
A
MX934 (DS7471) PIR Detector
200
μ
A
200
μ
A
MX938 (DS7472) PIR Detector
200
μ
A
200
μ
A
MX950 (DS7476) TriTech
®
PIR/Microwave Detector 6 mA 35 mA
RF3222 Wireless Receivers 30 mA 30 mA
2-Wire Smoke Detectors
4-Wire Smoke Detectors
Bells, Horns, etc.
Other Sensors
Other
Grand Total
Grand Total
Max. Load Currents Standby Alarm
UL Installations 1.5 A 2.5 A
Maximum Current By Output:
Not to exceed the maximum load currents listed above in Standby or Alarm
Aux. Power & Keypad (Combined) 1.0 A 1.0 A
Option Power 1.0 A 1.0 A
Bell Output X 1.75 A
Programmable Output 2 500 mA 500 mA
Loop Power + 500 mA 500 mA

Table of Contents