Panel Controller Maintenance – walktest | en 71
Bosch Sicherheitssysteme GmbH Operation guide F.01U.076.969 | 6.0 | 2010.04
Example:
1. Select Walktest group.
2. Select Sequential walktest or Simultaneous walktest
A list of walktest groups is displayed. Refer to Section 5.6.1 Scrolling through lists,
page 28 for information on how to navigate through a list.
3. Select the list field you require.
The field is marked.
4. Select On.
The selected walktest group is switched to walktest.
15.2.2 Ending the walktest
To end the walktest for this walktest group:
1. Mark the selected walktest group.
2. Select Off.
15.3 Ending walktest for all elements
To end the walktest for all walktest groups and elements:
1. Select End from the status bar.
Various possibilities are offered on the display:
2. Select Yes in order to end the walktest for all walktest groups and elements.
Select No to cancel the operation and return to the previous display.
The walktest is ended for all walktest groups.
15.4 Displaying tested or untested elements
Select Exit from the status bar.
The following options are offered for the walktest currently being performed:
Select Not tested to display the elements that showed no reaction during the test or that
have not been tested.
Select Tested to display the elements that were tested and showed a reaction.
NOTICE!
You can choose to display either the untested or tested elements in the current walktest.