Conventional Fire Panel | en 29
Bosch Sicherheitssysteme GmbH Operation Guide F.01U.172.982 | 5.0 | 2012.04
A Appendix
A.1 Event Memory
Message Meaning
Drill/Evacuate A manual alarm has been triggered on the panel.
Zone # Alarm Zone # has triggered an alarm.
Zone # PreAlarm Zone # has triggered a pre-alarm.
Zone # Open Zone # is interrupted.
Zone # Short Zone # has a short-circuit.
Zone # Normal Zone # is in the normal state. (Fault or alarm
eliminated)
Zone # Disabled Zone # is disabled.
Zone # Enabled Zone # was enabled.
Input # Open Input # interrupted.
Input # Short Input # short-circuit.
Input # Normal Input # normal.
Aux Power Short Short-circuit in the AUX power supply
Aux Power Normal Fault in the AUX power supply rectified.
NAC # Open Notification appliance #, line interrupted
NAC # Short Notification appliance #, short-circuit on line.
NAC # Normal Notification appliance # normal. (Fault was
eliminated)
NAC Enabled Notification appliances re-enabled.
NAC Disabled Notification appliances disabled.
Relays Enabled Relays re-enabled.
Relays Disabled Relays disabled.
Battery Fault Fault in the battery power supply.
Battery Restore Battery power supply was restored.
Mains Fault Fault in the 230 V power supply.
Mains Restore 230 V power supply was restored.
Ext PS Fault Fault in external power supply unit.
Ext PS Normal Fault in external power supply unit resolved.
Ext BATT Fault Fault in external battery.
Ext BATT Normal Fault in external battery resolved.
Sys Load Fault Current consumption of panel and all connected
peripherals is above 3.5 A.
Sys Load Normal Current consumption is back in permitted range.
System Fault System fault
Panel boot-up Panel has been restarted.
Reset Panel Panel has been reset.