Conventional Fire Panel System Overview | en 9
Bosch Sicherheitssysteme GmbH Operation Guide F.01U.172.982 | 5.0 | 2012.04
Alarms
Display of alarms. Zones that have triggered an alarm are
flagged.
In addition, the total number of alarms is displayed in the
bottom line, along with the sequence of the triggered alarms.
3.4 Operating Levels
This fire panel has three operating levels. You can only perform
certain actions on certain operating levels.
Code inputs are necessary for accessing operating levels 2 and
3.
Operating level 2 can be accessed using the optional key or an
input with the appropriate configuration.
Fire Alarms: 1
1 2 3 4 5 6 7 8
| ? | | | | | |
Level 1 Display information
Read out event memory
Display faults and deactivations
Perform display test
Level 2 Change language and time/date
Switch key tones on/off
Put zones in test mode and take zones out of test mode
Switch off/on zones, notification appliances, relays and
transistor outputs
Trigger evacuations
Reset panel
Switch between day/night mode
All actions of level 1
Level 3 All settings for installing and programming the system.