Notes on installation and operation | 21
6720872361 (2017/04)Greenstar combi 100 p / 151 p
Table 10 Corrosive materials
Surface temperature
The max. surface temperature of this appliance is below 185 °F (85 °C).
According to ANSI/Z223.1/NFPA54 (National fuel gas code) and CAN/
CGA B 149.1 (Natural Gas and Propane installation code), the appliance
is approved for zero clearance to combustibles. For servicing a clearance
of 4" (102 mm) is recommended.
6.4 Pre-installing pipes
▶ Secure the installation template supplied with the technical
documentation to the wall; when doing so, observe the minimum side
clearances of 4 inches (102 mm) ( page 7).
▶ Drill holes for the appliance and for the hydraulics connection plate in
accordance with the mounting template.
Fig. 11 Mounting template
NOTICE:
For walls with insufficient load capacity, the appliance and the
hydraulics connection plate must be mounted on a sheet of plywood or
similar reinforcement.
▶ Remove the mounting template.
NOTICE:
The hydraulics connection plate (packed in cardboard) can be found in
the air box of the appliance.
▶ Secure the hydraulics connection plate and the mounting bracket
with the mounting kits supplied.
Fig. 12 Installing the hydraulics connection plate
Fig. 13 Hydraulics connection plate (front view)
[1] Heating supply, R 1" NPT
[2] DHW, R 3/4" NPT
[3] Gas, R 3/4" NPT
[4] Cold water, R 3/4" NPT
[5] Heating return, R 1" NPT
Household sources
Cleaning and
degreasing agents
Perchloroethylene, methylchloroform,
trichloroethylene, methylene chloride, carbon
tetrachloride, hydrochloric acid
Workshop
Solvents and thinners Various chlorinated hydrocarbons
Aerosols Chlorofluorinated hydrocarbons
(difluorodichloromethane)
0010014681-001
( 17 11/18 in. )
0010014680-001
==
6 720 641 933-90.1O
1 3/16
"
(30 mm)
7 7/8"
(200 mm)
54321