Bosch LV012 - User Manual

Bosch LV012
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Installation and Maintenance Manual
LV MODEL
8733944336 (2016/09)

Table of Contents

Questions and Answers

  • A
    Audrey McmahonSep 23, 2025
    What causes water hammer in my Bosch Heat Pump and how to fix it?
    • C
      Chris ThompsonSep 23, 2025
      If you're experiencing water hammer with your Bosch Heat Pump, the cause may be fast closing valves. In this case, change the valves to a slow-close type.
  • W
    wbrownAug 23, 2025
    How to reduce objectionable noise levels from my Bosch LV012 Heat Pump?
    • L
      lorimitchellAug 23, 2025
      If you're experiencing objectionable noise levels from your Bosch Heat Pump, ensure the duct work and grilles are properly sized for unit air flow. If the fan speed setting is too high, consult the blower performance table and reduce fan speed if possible. To address structure borne noise, mount the unit on a vibration pad. Also, install the unit in accordance with the provided instructions and adjust the unit location to prevent it from touching the structure.
  • R
    Rebecca HernandezAug 25, 2025
    What to do if my Bosch LV012 Heat Pump compressor isn't running and the fan is on, but I suspect low refrigerant?
    • K
      Kathleen BarronAug 26, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a low-pressure fault caused by low refrigerant. Check the refrigerant pressure with a gauge set.
  • S
    Sean CallahanAug 26, 2025
    What to do if the compressor of my Bosch LV012 Heat Pump doesn't work but the fan runs and there is a freeze fault?
    • N
      Nicole HunterAug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a freeze fault in the water coil caused by no or low water flow. Check the water valves and/or pumps to ensure they are operating correctly. Also, check the water coil for any blockages.
  • T
    Travis CoxAug 27, 2025
    Why is my Bosch LV012 Heat Pump compressor not running but the fan is, possibly due to high water temperature?
    • J
      Jessica LongAug 28, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by high water temperature. Check the water temperature to ensure it is within the appropriate range.
  • D
    Danielle ParkerSep 17, 2025
    What to do if the fan is not working on my Bosch LV012 Heat Pump with a PSC motor?
    • A
      Ashley JimenezSep 17, 2025
      If the fan on your Bosch Heat Pump isn't working (PSC motor), first check the supply voltage from the fan relay to the motor and ensure that all motor wires are secure. With the power off, spin the motor shaft; noise, resistance, or uneven motion can indicate motor failure. Also, check for 24 VAC across the fan relay coil and check all wiring connections. If the relay coil is energized but the relay does not pull in, check the resistance across the relay coil; an open circuit indicates a faulty relay.
  • D
    David LewisSep 14, 2025
    What to do if the compressor is not working but the fan runs on my Bosch Heat Pump, and it might be related to a brown out fault?
    • T
      tweaverSep 14, 2025
      If the compressor of your Bosch Heat Pump isn't working, but the fan is still running, it could be due to a brown out fault. This could be caused by low supply voltage, so check the primary voltage to ensure it is within the limits listed on the unit data plate. Another cause may be an overloaded control circuit; if the control voltage is below 18 V, check accessories connected to the unit and ensure that they do not exceed the VA draw. A bad thermostat connection can also cause this issue, so check that the thermostat wiring is the proper gauge and length, that it is not damaged, and that all connections at the thermostat and heat pump are secure.
  • C
    Connor LynchSep 15, 2025
    What to do if the compressor is not working but the fan runs on my Bosch LV012 Heat Pump, and it might be related to thermostat?
    • J
      Julie FergusonSep 15, 2025
      If the compressor of your Bosch Heat Pump isn't working, but the fan is still running, ensure that the thermostat is on and calling for 'Y'. Check the 'Y' connection from the thermostat, ensuring that there is 24 VAC between 'Y' and 'C'. Also, check the wiring to ensure that there is 24 VAC across the contactor coil. Finally, test the contactor with 24VAC (between 'R' and 'C'). Ohm the contactor coil; an open circuit indicates a burned coil.
  • W
    Walter LopezSep 6, 2025
    Why is my Bosch LV012 compressor not running, but the fan is, possibly due to condensate drainage issues?
    • H
      Heather DavenportSep 6, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a condensate fault caused by poor drainage. Check the condensate pan for a high water level. Check the drain line for blockages, double trapping, or inadequate trapping.
  • C
    Christina NelsonSep 3, 2025
    How to troubleshoot a Bosch LV012 with no compressor operation but running fan, possibly due to a bad thermostat connection?
    • T
      tmathewsSep 3, 2025
      If the compressor of your Bosch Heat Pump is not working, but the fan is running, it might be due to a brown-out fault caused by a bad thermostat connection. Check that the thermostat wiring is of the proper gauge and length, is undamaged, and that all connections at the thermostat and heat pump are secure.

Summary

Key to Symbols

Warnings and Symbols

Defines warning keywords and symbols used throughout the manual.

Safety Warnings

General Safety Precautions

Emphasizes reading the manual, proper installation, and qualified personnel.

Installation Guide

Site Prep, Unit Check, and Location

Initial checks, unit inspection, and selecting the installation site.

Pre-Start-Up and Operation

System Checkout and Limits

Verifying system readiness, operating limits, and starting conditions.

Fan Motor Options

Troubleshooting Guide

Compressor and Fan Operation Issues

Diagnosing problems with compressor or fan operation and fault codes.

Airflow, Mode, and Noise Issues

Addressing airflow, mode shifting, humidity, and noise problems.

Technical Data Tables

Maintenance and Decommissioning

Maintenance Procedures

Guidelines for filter changes, annual check-ups, and condensate drain maintenance.

Unit Check Out Sheet

Bosch LV012 Specifications

General IconGeneral
BrandBosch
ModelLV012
CategoryHeat Pump
LanguageEnglish