Installation and Maintenance Manual
LV MODEL
8733944336 (2016/09)

Table of Contents

Questions and Answers

  • B
    brandon49Sep 23, 2025
    What causes water hammer in my Bosch LV024 and how to fix it?
    • S
      Sean SimpsonSep 23, 2025
      If you're experiencing water hammer with your Bosch Heat Pump, the cause may be fast closing valves. In this case, change the valves to a slow-close type.
  • C
    Cameron PerezAug 23, 2025
    How to reduce objectionable noise levels from my Bosch Heat Pump?
    • S
      Scott ThompsonAug 23, 2025
      If you're experiencing objectionable noise levels from your Bosch Heat Pump, ensure the duct work and grilles are properly sized for unit air flow. If the fan speed setting is too high, consult the blower performance table and reduce fan speed if possible. To address structure borne noise, mount the unit on a vibration pad. Also, install the unit in accordance with the provided instructions and adjust the unit location to prevent it from touching the structure.
  • B
    brendalamAug 25, 2025
    What to do if my Bosch LV024 compressor isn't running and the fan is on, but I suspect low refrigerant?
    • B
      Brenda PetersAug 26, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a low-pressure fault caused by low refrigerant. Check the refrigerant pressure with a gauge set.
  • B
    Brittany PerezAug 27, 2025
    What to do if the compressor of my Bosch Heat Pump doesn't work but the fan runs and there is a freeze fault?
    • A
      andrea59Aug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a freeze fault in the water coil caused by no or low water flow. Check the water valves and/or pumps to ensure they are operating correctly. Also, check the water coil for any blockages.
  • J
    Jeffrey FinleyAug 27, 2025
    Why is my Bosch LV024 Heat Pump compressor not running but the fan is, possibly due to high water temperature?
    • J
      john37Aug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by high water temperature. Check the water temperature to ensure it is within the appropriate range.
  • J
    Jeremy TurnerSep 17, 2025
    What to do if the fan is not working on my Bosch Heat Pump with a PSC motor?
    • L
      lucasestesSep 18, 2025
      If the fan on your Bosch Heat Pump isn't working (PSC motor), first check the supply voltage from the fan relay to the motor and ensure that all motor wires are secure. With the power off, spin the motor shaft; noise, resistance, or uneven motion can indicate motor failure. Also, check for 24 VAC across the fan relay coil and check all wiring connections. If the relay coil is energized but the relay does not pull in, check the resistance across the relay coil; an open circuit indicates a faulty relay.
  • T
    Tyler HaynesSep 14, 2025
    What to do if the compressor is not working but the fan runs on my Bosch Heat Pump, and it might be related to a brown out fault?
    • R
      Rebecca JonesSep 14, 2025
      If the compressor of your Bosch Heat Pump isn't working, but the fan is still running, it could be due to a brown out fault. This could be caused by low supply voltage, so check the primary voltage to ensure it is within the limits listed on the unit data plate. Another cause may be an overloaded control circuit; if the control voltage is below 18 V, check accessories connected to the unit and ensure that they do not exceed the VA draw. A bad thermostat connection can also cause this issue, so check that the thermostat wiring is the proper gauge and length, that it is not damaged, and that all connections at the thermostat and heat pump are secure.
  • G
    Gwendolyn JohnsonSep 15, 2025
    What to do if the compressor is not working but the fan runs on my Bosch Heat Pump, and it might be related to thermostat?
    • Q
      qbrownSep 16, 2025
      If the compressor of your Bosch Heat Pump isn't working, but the fan is still running, ensure that the thermostat is on and calling for 'Y'. Check the 'Y' connection from the thermostat, ensuring that there is 24 VAC between 'Y' and 'C'. Also, check the wiring to ensure that there is 24 VAC across the contactor coil. Finally, test the contactor with 24VAC (between 'R' and 'C'). Ohm the contactor coil; an open circuit indicates a burned coil.
  • J
    Joshua DaltonSep 6, 2025
    Why is my Bosch LV024 Heat Pump compressor not running, but the fan is, possibly due to condensate drainage issues?
    • J
      Jennifer MontoyaSep 6, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a condensate fault caused by poor drainage. Check the condensate pan for a high water level. Check the drain line for blockages, double trapping, or inadequate trapping.
  • P
    Pamela GarciaSep 3, 2025
    How to troubleshoot a Bosch LV024 with no compressor operation but running fan, possibly due to a bad thermostat connection?
    • K
      Kelli JamesSep 3, 2025
      If the compressor of your Bosch Heat Pump is not working, but the fan is running, it might be due to a brown-out fault caused by a bad thermostat connection. Check that the thermostat wiring is of the proper gauge and length, is undamaged, and that all connections at the thermostat and heat pump are secure.

Summary

KEY TO SYMBOLS

Warnings

Explains warning symbols and keywords for risk identification and severity.

SAFETY WARNINGS

DANGER and WARNING

Highlights severe hazards, potential for death, serious injury, or property damage.

INSTALLATION

INSTALLATION - SITE PREPARATION

Step 3: Locate Unit

Guides selection of optimal indoor location, ensuring service access and proper airflow.

Step 4: Mount The Unit

Provides instructions for mounting vertical and horizontal units, including vibration isolation and pitching.

INSTALLATION - UNIT MOUNTING

INSTALLATION - HANGING BRACKET KIT

Hanging Bracket Installation Instructions

Step-by-step guide for installing the hanging bracket kit for suspended unit mounting.

Safety Precautions for Hanging

Critical warnings regarding screw reuse, code compliance, and secure ceiling anchoring.

INSTALLATION - DUCT AND DRAIN

INSTALLATION - PIPING AND WIRING

Step 8: Wire Field Power Supply

Detailed instructions for high voltage power supply wiring, including safety and compliance notes.

INSTALLATION - ELECTRICAL CONNECTIONS

INSTALLATION - UNIT CONTROLS

Step 9: Wire Field Controls

Procedures for wiring field controls, including ECM interface board and thermostat connections.

SAFETY FEATURES AND UPM BOARD

Unit Safety Features

Details on high/low pressure switches, freeze protection sensors, and condensate overflow protection.

UNIT PROTECTION AND FAULT CODES

PRE-START-UP CHECKS

System Checkout

Essential checks before initial unit startup, including voltage, connections, and piping.

START-UP PROCEDURES

Scroll Compressor Rotation Check

How to verify correct compressor rotation direction for proper operation and to prevent damage.

SEQUENCE OF OPERATION

ECM CONTROL BOARD SEQUENCE

UNIT START-UP MODES

Cooling Mode Start-Up

Steps for initiating and verifying proper operation in the cooling cycle.

Heating Mode Start-Up

Steps for initiating and verifying proper operation in the heating cycle.

APPLICATION CONSIDERATIONS

WATER SYSTEM APPLICATIONS

WATER QUALITY CONSIDERATIONS

PIPING GUIDELINES

FAN MOTOR OPTIONS

FAN MOTOR SPECIFICATIONS

Constant Torque ECM Motors

Details on ECM motor efficiency, speed settings, and performance for constant torque applications.

FAN MOTOR TYPES

Constant Airflow ECM Motors

Features of ECM motors for constant airflow, including ventilation and dehumidification modes.

TROUBLESHOOTING GUIDE

No Compressor Operation, Fan Runs

Troubleshooting steps for faults indicated by LED blinking, related to pressure or freeze conditions.

TROUBLESHOOTING - FAULT INDICATIONS

No Compressor, Fan Runs - Condensate;Brown Out;Freeze Faults

Diagnosing issues based on LED blink codes for condensate, brown out, and freeze conditions.

No Compressor, Fan Runs - Thermostat;Wiring Issues

Troubleshooting thermostat connections and wiring for compressor operation failures.

TROUBLESHOOTING - DRIVE COMPONENT ISSUES

No Compressor Operation

Diagnosing compressor overload, wiring issues, and potential motor failure.

No Power or Fan Operation

Troubleshooting low/no supply power, faulty transformer, and fan relay issues.

TROUBLESHOOTING - AIRFLOW AND MODE ISSUES

Fan Operation Issues

Troubleshooting no fan operation signals, loose wiring, and interface board problems.

TROUBLESHOOTING - ENVIRONMENTAL AND NOISE ISSUES

WIRING DIAGRAMS

MAINTENANCE SCHEDULE

INFORMATION ON DECOMMISSIONING

UNIT CHECK OUT SHEET

Bosch LV024 Specifications

General IconGeneral
BrandBosch
ModelLV024
CategoryHeat Pump
LanguageEnglish