Installation and Maintenance Manual
LV MODEL
8733944336 (2016/09)

Table of Contents

Questions and Answers

  • S
    stephanie00Sep 7, 2025
    How to troubleshoot a Bosch LV024 Heat Pump with no compressor operation but running fan, possibly due to blocked return air?
    • J
      John WellsSep 7, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a condensate fault caused by blocked return air. Check the condensate pan for a high water level. Also, check the air filter and return air duct work for blockage, and ensure there is adequate space between the return air opening and any obstructions.
  • K
    kbrockAug 22, 2025
    Why is my Bosch LV024 Heat Pump not shifting into cooling?
    • J
      Jennifer WalterAug 22, 2025
      If your Bosch Heat Pump isn't shifting into cooling mode, check that the reversing valve solenoid is receiving 24 VAC. If it is, check the resistance of the solenoid; an open circuit may indicate a burned out solenoid. Also, check that the reversing valve thermostat wire is connected to the 'O' terminal of the thermostat and check for a contact closure between 'O' and 'R'. Finally, check that the wires from the thermostat to the unit are securely connected and that the wires from the electrical box to the reversing valve are connected.
  • S
    Shawn HowardSep 4, 2025
    What to do if the compressor of my Bosch LV024 Heat Pump doesn't work but the fan runs and there is a freeze fault caused by low refrigerant?
    • M
      Matthew WaltersSep 5, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a freeze fault in the air coil caused by low refrigerant. Check the refrigerant pressure with a gauge set.
  • P
    Pamela GarciaSep 3, 2025
    How to troubleshoot a Bosch LV024 with no compressor operation but running fan, possibly due to a bad thermostat connection?
    • K
      Kelli JamesSep 3, 2025
      If the compressor of your Bosch Heat Pump is not working, but the fan is running, it might be due to a brown-out fault caused by a bad thermostat connection. Check that the thermostat wiring is of the proper gauge and length, is undamaged, and that all connections at the thermostat and heat pump are secure.
  • J
    jprestonSep 2, 2025
    What to do if my Bosch Heat Pump compressor isn't running but the fan is on and I suspect an overloaded control circuit?
    • T
      Tiffany MoralesSep 2, 2025
      If the compressor of your Bosch Heat Pump is not working, but the fan is running, it might be due to a brown-out fault caused by an overloaded control circuit. Check the control voltage; if it's below 18V, inspect the accessories connected to the unit and ensure they don't exceed the VA draw.
  • B
    Brianna DavisAug 31, 2025
    Why is my Bosch LV024 compressor not running but the fan is, possibly due to low airflow?
    • V
      Valerie Decker DDSSep 1, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a low-pressure fault caused by no or low airflow. Check the fan motor to ensure it is operating correctly.
  • L
    Linda ShepardAug 30, 2025
    What to do if my Bosch Heat Pump compressor isn't running but the fan is, and I suspect airflow issues?
    • H
      halljoeAug 30, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by no or low airflow. Check the fan motor to ensure it is operating correctly.
  • K
    Kerry Nielsen DDSAug 29, 2025
    How to troubleshoot a Bosch LV024 Heat Pump with no compressor operation but running fan, possibly due to a fouled water coil?
    • E
      Emily DanielsAug 29, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by a fouled or scaled water coil. Check for proper flow rate and water temperature, especially looking for a low water side temperature rise during cooling.
  • J
    Jeffrey FinleyAug 27, 2025
    Why is my Bosch LV024 Heat Pump compressor not running but the fan is, possibly due to high water temperature?
    • J
      john37Aug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by high water temperature. Check the water temperature to ensure it is within the appropriate range.
  • B
    Brittany PerezAug 27, 2025
    What to do if the compressor of my Bosch Heat Pump doesn't work but the fan runs and there is a freeze fault?
    • A
      andrea59Aug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a freeze fault in the water coil caused by no or low water flow. Check the water valves and/or pumps to ensure they are operating correctly. Also, check the water coil for any blockages.

Summary

KEY TO SYMBOLS

Warnings

Explains warning symbols and keywords for risk identification and severity.

SAFETY WARNINGS

DANGER and WARNING

Highlights severe hazards, potential for death, serious injury, or property damage.

INSTALLATION

INSTALLATION - SITE PREPARATION

Step 3: Locate Unit

Guides selection of optimal indoor location, ensuring service access and proper airflow.

Step 4: Mount The Unit

Provides instructions for mounting vertical and horizontal units, including vibration isolation and pitching.

INSTALLATION - UNIT MOUNTING

INSTALLATION - HANGING BRACKET KIT

Hanging Bracket Installation Instructions

Step-by-step guide for installing the hanging bracket kit for suspended unit mounting.

Safety Precautions for Hanging

Critical warnings regarding screw reuse, code compliance, and secure ceiling anchoring.

INSTALLATION - DUCT AND DRAIN

INSTALLATION - PIPING AND WIRING

Step 8: Wire Field Power Supply

Detailed instructions for high voltage power supply wiring, including safety and compliance notes.

INSTALLATION - ELECTRICAL CONNECTIONS

INSTALLATION - UNIT CONTROLS

Step 9: Wire Field Controls

Procedures for wiring field controls, including ECM interface board and thermostat connections.

SAFETY FEATURES AND UPM BOARD

Unit Safety Features

Details on high/low pressure switches, freeze protection sensors, and condensate overflow protection.

UNIT PROTECTION AND FAULT CODES

PRE-START-UP CHECKS

System Checkout

Essential checks before initial unit startup, including voltage, connections, and piping.

START-UP PROCEDURES

Scroll Compressor Rotation Check

How to verify correct compressor rotation direction for proper operation and to prevent damage.

SEQUENCE OF OPERATION

ECM CONTROL BOARD SEQUENCE

UNIT START-UP MODES

Cooling Mode Start-Up

Steps for initiating and verifying proper operation in the cooling cycle.

Heating Mode Start-Up

Steps for initiating and verifying proper operation in the heating cycle.

APPLICATION CONSIDERATIONS

WATER SYSTEM APPLICATIONS

WATER QUALITY CONSIDERATIONS

PIPING GUIDELINES

FAN MOTOR OPTIONS

FAN MOTOR SPECIFICATIONS

Constant Torque ECM Motors

Details on ECM motor efficiency, speed settings, and performance for constant torque applications.

FAN MOTOR TYPES

Constant Airflow ECM Motors

Features of ECM motors for constant airflow, including ventilation and dehumidification modes.

TROUBLESHOOTING GUIDE

No Compressor Operation, Fan Runs

Troubleshooting steps for faults indicated by LED blinking, related to pressure or freeze conditions.

TROUBLESHOOTING - FAULT INDICATIONS

No Compressor, Fan Runs - Condensate;Brown Out;Freeze Faults

Diagnosing issues based on LED blink codes for condensate, brown out, and freeze conditions.

No Compressor, Fan Runs - Thermostat;Wiring Issues

Troubleshooting thermostat connections and wiring for compressor operation failures.

TROUBLESHOOTING - DRIVE COMPONENT ISSUES

No Compressor Operation

Diagnosing compressor overload, wiring issues, and potential motor failure.

No Power or Fan Operation

Troubleshooting low/no supply power, faulty transformer, and fan relay issues.

TROUBLESHOOTING - AIRFLOW AND MODE ISSUES

Fan Operation Issues

Troubleshooting no fan operation signals, loose wiring, and interface board problems.

TROUBLESHOOTING - ENVIRONMENTAL AND NOISE ISSUES

WIRING DIAGRAMS

MAINTENANCE SCHEDULE

INFORMATION ON DECOMMISSIONING

UNIT CHECK OUT SHEET

Bosch LV024 Specifications

General IconGeneral
BrandBosch
ModelLV024
CategoryHeat Pump
LanguageEnglish