Installation and Maintenance Manual
LV MODEL
8733944336 (2016/09)

Table of Contents

Questions and Answers

  • R
    Richard FrySep 23, 2025
    What causes water hammer in my Bosch LV048 Heat Pump and how to fix it?
    • S
      Steven DavisSep 23, 2025
      If you're experiencing water hammer with your Bosch Heat Pump, the cause may be fast closing valves. In this case, change the valves to a slow-close type.
  • T
    Terrance WhitneyAug 23, 2025
    How to reduce objectionable noise levels from my Bosch LV048?
    • B
      Brent WalkerAug 23, 2025
      If you're experiencing objectionable noise levels from your Bosch Heat Pump, ensure the duct work and grilles are properly sized for unit air flow. If the fan speed setting is too high, consult the blower performance table and reduce fan speed if possible. To address structure borne noise, mount the unit on a vibration pad. Also, install the unit in accordance with the provided instructions and adjust the unit location to prevent it from touching the structure.
  • M
    michaelhunterAug 25, 2025
    What to do if my Bosch LV048 Heat Pump compressor isn't running and the fan is on, but I suspect low refrigerant?
    • M
      Miguel LopezAug 26, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a low-pressure fault caused by low refrigerant. Check the refrigerant pressure with a gauge set.
  • S
    smithmeganAug 27, 2025
    What to do if the compressor of my Bosch LV048 Heat Pump doesn't work but the fan runs and there is a freeze fault?
    • S
      Shane MillsAug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a freeze fault in the water coil caused by no or low water flow. Check the water valves and/or pumps to ensure they are operating correctly. Also, check the water coil for any blockages.
  • R
    rphillipsAug 27, 2025
    Why is my Bosch LV048 compressor not running but the fan is, possibly due to high water temperature?
    • R
      ronald20Aug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by high water temperature. Check the water temperature to ensure it is within the appropriate range.
  • G
    Gregory BurnsSep 17, 2025
    What to do if the fan is not working on my Bosch LV048 Heat Pump with a PSC motor?
    • B
      Brittany ParkSep 17, 2025
      If the fan on your Bosch Heat Pump isn't working (PSC motor), first check the supply voltage from the fan relay to the motor and ensure that all motor wires are secure. With the power off, spin the motor shaft; noise, resistance, or uneven motion can indicate motor failure. Also, check for 24 VAC across the fan relay coil and check all wiring connections. If the relay coil is energized but the relay does not pull in, check the resistance across the relay coil; an open circuit indicates a faulty relay.
  • K
    Kaitlin DiazSep 14, 2025
    What to do if the compressor is not working but the fan runs on my Bosch LV048, and it might be related to a brown out fault?
    • T
      Thomas HernandezSep 14, 2025
      If the compressor of your Bosch Heat Pump isn't working, but the fan is still running, it could be due to a brown out fault. This could be caused by low supply voltage, so check the primary voltage to ensure it is within the limits listed on the unit data plate. Another cause may be an overloaded control circuit; if the control voltage is below 18 V, check accessories connected to the unit and ensure that they do not exceed the VA draw. A bad thermostat connection can also cause this issue, so check that the thermostat wiring is the proper gauge and length, that it is not damaged, and that all connections at the thermostat and heat pump are secure.
  • G
    Gregory ButlerSep 15, 2025
    What to do if the compressor is not working but the fan runs on my Bosch Heat Pump, and it might be related to thermostat?
    • A
      Austin SimpsonSep 15, 2025
      If the compressor of your Bosch Heat Pump isn't working, but the fan is still running, ensure that the thermostat is on and calling for 'Y'. Check the 'Y' connection from the thermostat, ensuring that there is 24 VAC between 'Y' and 'C'. Also, check the wiring to ensure that there is 24 VAC across the contactor coil. Finally, test the contactor with 24VAC (between 'R' and 'C'). Ohm the contactor coil; an open circuit indicates a burned coil.
  • A
    amillerSep 6, 2025
    Why is my Bosch Heat Pump compressor not running, but the fan is, possibly due to condensate drainage issues?
    • N
      Nicholas HintonSep 6, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a condensate fault caused by poor drainage. Check the condensate pan for a high water level. Check the drain line for blockages, double trapping, or inadequate trapping.
  • D
    Dr. David Murphy Jr.Sep 3, 2025
    How to troubleshoot a Bosch LV048 with no compressor operation but running fan, possibly due to a bad thermostat connection?
    • N
      nicole51Sep 3, 2025
      If the compressor of your Bosch Heat Pump is not working, but the fan is running, it might be due to a brown-out fault caused by a bad thermostat connection. Check that the thermostat wiring is of the proper gauge and length, is undamaged, and that all connections at the thermostat and heat pump are secure.

Summary

KEY TO SYMBOLS

Warnings and Safety Precautions

Defines risk keywords and provides safety instructions for installation and servicing.

INSTALLATION GUIDE

Piping and Electrical Wiring

Details on water piping connections and high voltage wiring, compliance with codes.

Safety Features and Reset Procedures

Explanation of safety features, UPM board functions, freeze protection, and reset procedures.

UNIT START-UP AND PRE-OPERATION

Pre-Start-Up Checks and Procedures

Checklist of pre-startup checks, coil cleaning, startup procedure, and operating limits.

Compressor Rotation and Startup

Procedures to check compressor rotation and verify startup parameters.

SEQUENCE OF OPERATION

ECM CONTROL BOARD DE-HUMIDIFICATION

UNIT STARTUP MODES

APPLICATION CONSIDERATIONS

WATER QUALITY MANAGEMENT

UNIT OPTIONS OVERVIEW

FAN MOTOR OPTIONS

TROUBLESHOOTING

Unit Troubleshooting Guide

Table detailing problems, checks, causes, and actions for unit troubleshooting.

OPERATING DATA

WIRING DIAGRAMS

DIMENSIONAL DRAWINGS

MAINTENANCE AND OPERATION

Maintenance Procedures

Guidance on filter changes, annual checkups, and condensate drain maintenance.

Bosch LV048 Specifications

General IconGeneral
CategoryHeat Pump
ManufacturerBosch
ModelLV048
Phase1
RefrigerantR-410A
Cooling Capacity48000 BTU/h
Heating Capacity48000 BTU/h