Number Symbol Element Description
3 Recessed button The button is protected to prevent it
from being pressed accidentally. Use a
pointed object (such as a ballpoint pen)
to press the button.
This button has the following functions:
– Silencing of the buzzer: If the
buzzer is active, press the button
briefly to deactivate the warning
tone.
– Find function: If the find function of
the device is activated, press this
button to deactivate the indicators.
– Displaying the CAN baud rate: Press
this button for at least one second.
Please refer to section Displaying
the CAN baud rate, page 35
– Indicator test: Press this button for
at least three seconds to activate all
indicators. All indicators (LEDs) at
the front panel light up as long as
the button is pressed (“LED test”)
and the internal buzzer is activated.
4
System fault indicator light This indicator lights yellow if a system
fault according EN 54-16 was detected.
5 Voice alarm indicator light This indicator lights red if the controller
is in voice alarm state according EN
54-16.
6 Network indicator light Indicates the Ethernet network status:
– Illuminated green: Successful data
communication to all configured
Ethernet devices has been
established.
– Flashing green: Ethernet connection
to at least one Ethernet device lost.
– Off: No Ethernet connection.
7 Standby indicator light This indicator lights up green when the
device is in standby mode.
8 Power indicator light This indicator lights up green when the
power supply is OK.
14
en | System overview PAVIRO Controller
08-May-2017 | 04 | F01U306900 Operation manual