20 | Service menu settings
Gaz 6000 W8 716 473 216 (2014/09)
9.2.2 Menu 2
To call up a service function in this menu:
▶ Hold down “Back”, + and – at the same time until L.1 is shown on the
display.
▶ Press + until L.2 is shown on the display.
▶ Press OK to make settings in menu 2.
▶ Press + or – to scroll through the menu's service functions.
Service function Possible settings/comments/displays
2.1.A Maximum output Some gas supply utilities charge a basic rate based on output.
The output can be limited to the specific heat demand between the minimum rated output
and maximum rated output.
Default setting is the maximum rated output.
▶ Set the output in per cent.
▶ Measure the gas flow rate and compare it with the information from the setting tables . If
they do not match, change the setting.
2.1.b Maximum output
(DHW)(N.A)
The output can be limited to the specific heat demand between the minimum rated output
and maximum rated output.
Default setting is the maximum rated output for DHW.
▶ Set the DHW output in percent.
▶ Measure the gas flow rate and compare it with the information from the setting tables.If
they do not match, change the setting.
2.2.b Maximum flow temperature The maximum flow temperature can be set to between 40 °C and 82 °C.
Default setting is 85.
2.3.d Minimum rated output (heating) The output can be set to any percentage value between the minimum and maximum rated
output.
The default setting is the minimum rated output (heating), which varies according to
appliance.
2.4.E Internal parameter Do not change value 0.
2.8.A Software version The current software version is displayed.
2.8.E Returning the appliance to its standard
settings
This service function enables you to reset the appliance to its standard settings.
Setting 00.
Table 12 Menu 2