7.2 Cooling Capacity / Air Flow
Table 5 – Expanded Ratings: DO-SC22Z9 / DI-XU22Z
Based on 992 L/s Rated Airflow
TC: Total Cooling Capacity
SC: Sensible Cooling Capacity
Figure 14 – DO-SC22Z9 / DI-XU22Z Capacity / Airflow Chart
19.5
19.7
19.9
20.1
20.3
20.5
20.7
20.9
21.1
21.3
21.5
21.7
21.9
22.1
22.3
22.5
22.7
900 925 950 975 1000 1025 1050 1075 1100
Toal Cooling Capacity KW
Airflow L/s 900 925 950 975 1000 1025 1050 1075 1100
Dry Coil
82 87 91 96 101 106 112 117 122
Wet Coil
Pa
103 108 114 120 127 133 140 146 153
Table 6 – Coil Static Pressure Drop - DI-XU22Z
Return Air Temperature
Dry Bulb
°C
Wet Bulb
°C
Dry Bulb
°C
Wet Bulb
°C
Dry Bulb
°C
Wet Bulb
°C
Air Temperature
Entering Outdoor Unit
°C
21 15 27 19 32 23
TC kW
19.7 22.7 23.7
27
SC kW
14.7 16.9 21.1
TC kW
19.2 22.1 23.1
30
SC kW
14.5 16.7 20.9
TC kW
18.3
21.1 22.1
35
SC kW
14.0
16.2 20.3
TC kW
17.4 20.0 20.9
40
SC kW
13.5 15.7 19.8
TC kW
16.3 18.8 20.2
43
SC kW
12.7 14.8 19.4
TC kW
14.7 16.9 19.4
46
SC kW
11.4 13.3 19.0
Rated Air
Flow
Minimum
Air Flow