What to do if the output signal stays at 5.25 Vdc in Brooks 5850 S Measuring Instruments?
- Ssamantha23Aug 12, 2025
If the output signal of your Brooks Measuring Instruments stays at approximately 5.25 Vdc or 21 mA, even when there is flow and regardless of the set point, it could be due to a few reasons. It might be that the valve is leaking or stuck open, in which case you should clean and/or adjust the control valve. Another possibility is that +15V is applied to the valve override input; check the valve override terminal (pin 12). Finally, a defective electronic board could also be the cause.