Main
menu
Sub
menu
Description Setting Comment Ex
work
s
25 Relay active during
missing radio signal.
00 = OFF
01 = ON
00
26 Relay switching state
(Low = Relay active
open, High = Relay
active closed)
00 = OFF
01 = ON
00
30 General settings
31 Flush cycle in days. 00 = OFF
(manual)
01 ... 07
days
Only on models with
flushing unit.
07
32 Setting the water hard-
ness.
01 = soft
02 =
medium
03 = hard
The water hardness
affects the interval of the
filter replacement indica-
tion.
02
33 Amount of days until the
filter requires replace-
ment.
0 - 98 =
Amounts
of days
The filter replacement
indicator shows in how
many days the filter must
be replaced (0–98 days).
After the filter replacement
the value must be set
manually back to 98.
98
34 Operation via external
timer or other 115 V
switch-on mechanism.
00 = OFF
01 = ON
Humidity target value is
set to 90%. The actual
value constantly shows
00%. The fan setting is
freely selectable.
00
35 Adjustment/control
interval of fan during
automatic operation
01 ... 10
min.
Depending on room size. 05
Operating the humidifier
2013-11-04Evaporation Humidifier B500 Professional42