50
Table 12 -- Orifice Size and Manifold Pressure for Gas Input Rate (CONT.)
(Tabulated Data Based on 21,000 Btuh High-- Heat/14,500 Btuh for Low--Heat Per Burner, Derated 4 Percent for Each 1000 Ft.
Above Sea level)
ALTITUDE RANGE
(FT.)
AVG. GAS
HEAT VALUE
AT ALTITUDE
(BTUH/CU
FT.)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
USA
Only
5001 to
6000
725 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
750 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
775 45 3.7/1.8 44 3.2/1.5 44 3.3/1.6 44 3.4/1.6
800 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8 44 3.2/1.5
825 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8
850 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7
875 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6
900 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7 47 3.7/1.7
ALTITUDE RANGE
(FT.)
AVG. GAS
HEAT VALUE
AT ALTITUDE
BTUH
CU FT.
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
USA
Only
6001 to
7000
675 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
700 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
725 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
750 46 3.6/1.7 46 3.8/1.8 45 3.7/1.8 45 3.8/1.8
775 46 3.4/1.6 46 3.5/1.7 46 3.6/1.7 46 3.8/1.8
800 47 3.6/1.7 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7
825 47 3.4/1.6 47 3.5/1.7 47 3.6/1.7 47 3.8/1.8
850 48 3.7/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7
ALTITUDE RANGE
(FT.)
AVG. GAS
HEAT VALUE
AT ALTITUDE
BTUH
CU FT.
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
USA
Only
7001 to
8000
650 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5
675 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
700 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8
725 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8
750 47 3.5/1.7 47 3.7/1.8 47 3.8/1.8 46 3.5/1.6
775 48 3.8/1.8 47 3.4/1.6 47 3.6/1.7 47 3.7/1.7
800 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8 47 3.4/1.6
825 48 3.3/1.6 48 3.5/1.6 48 3.6/1.7 48 3.7/1.8
ALTITUDE RANGE
(FT.)
AVG. GAS
HEAT VALUE
AT ALTITUDE
BTUH
CU FT.
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
USA
Only
8001 to
9000
625 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
650 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8
675 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7 46 3.7/1.7
700 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6
725 48 3.7/1.8 48 3.8/1.8 47 3.5/1.7 47 3.6/1.7
750 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8
775 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7
U.S.A
.Only
9001 to
10,000
600 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.7/1.8
625 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7
650 47 3.4/1.6 47 3.6/1.7 47 3.7/1.8 47 3.8/1.8
675 48 3.6/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7
700 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8
725 49 3.7/1.8 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7
* Orifice numbers 43 are factory installed
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury or death, or property damage.
Before servicing, disconnect all electrical power to furnace.
Verify proper operation after servicing.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper
furnace operation or failure of furnace.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation.
CAUTION
!
Introduction
GENERAL
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of
315A