EasyManua.ls Logo

Bryant 330AAV - Non-Adaptive Heating Mode; Cooling Mode

Bryant 330AAV
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
or high-gas-heat speed. Simultaneously, the EAC termi-
nals EAC-1 and EAC-2 are energized with 115v and
remain energized as long as blower motor BLWM is
energized.
f. Switching from low- to high-gas heatIf furnace control
CPU switches from low-gas heat to high-gas heat, the
control CPU switches inducer motor IDM speed from
low to high. The high-heat pressure switch relay HPSR
closes. When inducer motor IDM provides sufficient
pressure to close the high-heat pressure switch HPS, the
high-heat gas valve solenoid GV is energized. The
blower motor BLWM switches speed for high-gas heat 5
sec after the control CPU switches from low-gas heat to
high-gas heat.
g. Switching from high- to low-gas heatThe control CPU
will not switch from high-gas heat to low-gas heat while
the thermostat R to W circuit is closed when a single-
stage thermostat is used.
h. Blower off delayWhen thermostat is satisfied, the
R-W circuit is opened, de-energizing gas valve GV,
stopping gas flow to burners, and de-energizing humidi-
fier terminals HUM and C
OM. The inducer motor IDM
remains energized for a 5 sec post-purge period. The
blower motor BLWM and EAC terminals EAC-1 and
EAC-2 remain energized for 90, 135, 180, or 225 sec
(depending on selection at blower off delay switches
SW-3 and SW-4). The furnace control CPU is factory set
for a 135-sec blower off delay.
2. Non-Adaptive Heating ModeTwo-Stage Thermostat and
2-Stage Heating
(See Fig. 10 for thermostat connections).
NOTE: The low-heat-only switch SW-2 in ON position selects
low-heat-only operation mode in response to closing the thermo-
stat R-W1 circuit. When high-heat-only switch SW-1 is in OFF
position, closing the thermostat R to W1 and W2 circuits is
required for high-gas-heat operation. When high-heat-only switch
SW-1 is on, it always causes high-gas-heat operation when R-W1
circuit is closed, regardless of the setting of the low-heat-only
switch SW-2 and regardless of whether R-W2 circuit is closed or
open.
When the wall thermostat "calls for heat", R-W/W1 circuit
closes for low-gas heat or R to W1-and-W2 circuits close
for high-gas heat. The furnace control performs a self
check, verifies low-heat and high-heat pressure switch
contacts LPS and HPS are open, and starts inducer motor
IDM in low speed or high speed as appropriate.
The start-up and shutdown functions and delays described
in item 1 above apply to 2-stage heating mode as well,
except for switching from low- to high-gas heat and vice
versa.
a. Switching from low- to high-gas heatIf thermostat
R-W/W1 circuit for low-gas heat is closed and R-W2
circuit for high-gas- heat closes, the control CPU
switches the inducer motor IDM speed from low to high.
The high-heat pressure switch relay HPSR closes. When
inducer motor IDM provides sufficient pressure to close
high-heat pressure switch HPS, the high-heat gas valve
solenoid GV is energized. The blower motor BLWM
switches speed for high-gas heat 5 sec after R-W2 circuit
closes.
b. Switching from high- to low-gas heatIf thermostat
R-W2 circuit for high-gas heat opens and R to W/W1
circuit for low-gas heat remains closed, the control CPU
will switch inducer motor IDM speed from high to low.
The high-heat pressure switch relay HPSR will open to
de-energize high-heat gas valve solenoid GV. When
inducer motor IDM reduces pressure sufficiently, the
high-heat pressure switch HPS will open. The low-heat
gas valve solenoid GV remains energized as long as
low-heat pressure switch LPS remains closed. The
blower motor BLWM switches speed for low-gas heat 5
sec after R-W2 circuit opens.
3. Cooling Mode
a. Single-Speed Cooling Outdoor Unit
(See Fig. 9 for thermostat connections.)
(1.) The thermostat closes R to G-and-Y circuits. The
R-Y circuit starts the outdoor unit, and R to
G-and-Y circuits start the furnace blower motor
BLWM on high-cool speed.
(2.) The EAC terminals EAC-1 and EAC-2 are ener-
gized with 115v when blower motor BLWM is
operating.
(3.) When thermostat is satisfied, the R to G-and-Y
circuits are opened. The outdoor unit stops, and
furnace blower motor BLWM continues operating
on high-cool speed for an additional 90 sec.
b. Two-Speed Cooling Outdoor Unit
(See Fig. 10 for thermostat connections.)
(1.) The thermostat closes R to G-and-Y1 circuits for
low cooling or closes R to G-and-Y1-and-Y/Y2
circuits for high cooling. The R to Y1 circuits start
the outdoor unit on low-cooling speed, and the R-G
circuit starts furnace blower motor BLWM on
low-cooling speed (same speed as for low-gas heat).
The R to Y1-and-Y2 circuits start the outdoor unit
on high-cooling speed, and the R to G-and-Y2
circuits start furnace blower motor BLWM on
high-cooling speed.
NOTE: Y1 is found in the outdoor unit. The furnace control CPU
controls blower motor BLWM speed by sensing only G for
low-cooling speed and Y/Y2 for high-cooling speed.
(2.) The EAC terminals EAC-1 and EAC-2 are ener-
gized with 115v when blower motor BLWM is
operating on either cooling speed.
Fig. 12Setup Switches on Control Center
(Factory Settings)
A96402
BLOWER-
OFF
DELAY
LOW
HEAT
(ADAPTIVE
ALGORITHM)
HIGH
HEAT
ONLY
43 2
OFF
ON
1
12

Other manuals for Bryant 330AAV

Related product manuals