EasyManuals Logo

Bryant 566D User Manual

Bryant 566D
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
79
APPLICATION DATA 524A
1. OPERATING LIMITS
Maximum fan speed 524A-B,C072-240 . . . . . . . .1200 rpm
Maximum fan speed 524A-B,C300 . . . 1100 rpm (18.3 r/s)
2. GENERAL Select equipment to match or to be slightly
less than peak load. This provides better humidity control,
less unit cycling, and less part-load operation. Equipment
should be selected to perform at no less than 300 cfm/ton.
The air handler fan must always be operating when the con-
densing unit is operating.
Ductwork should be sized according to unit size, not build-
ing load. For larger units with two fans, a split duct transition
is recommended at the fan outlets, but a plenum can
be used with slight reduction in external static pressure
capability.
FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA
*Danfoss part numbers shown.
†Sporlan Valve Co. part numbers shown.
NOTE: Hot gas bypass applications require field-supplied auxiliary side
connector.
FAN MOTOR DATA
STANDARD MOTOR
LEGEND
NEMA National Electrical Manufacturers Association
UNIT
COIL
TYPE
TXV
Qty...Part No.*
DISTRIBUTOR
Qty...Part No.†
FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
NOZZLE
Qty...Part No.
524A-B,C 072 3, 4 Row 1...TDEBX8 1...1116 12...
1
/
4
1...E5
524A-B,C 090 3, 4 Row 1...TDEBX8 1...1126 15...
1
/
4
1...C6
524A-B,C 120 3, 4 Row 2...TDEX6 2...1115 9...
1
/
4
2...E4
524A-B 150 3 Row 2...TDEBX8 2...1115 9...
1
/
4
2...E5
524A-C 150 4 Row 2...TDEBX8 2...1115 12...
3
/
16
2...E5
524A-B 180 3 Row 2...TDEBX8 2...1116 12...
1
/
4
2...E6
524A-C 180 4 Row 2...TDEBX8 2...1126 16...
1
/
4
2...C6
524A-B 240 3 Row 2...TDEBX11 2...1116 13...
1
/
4
2...E8
524A-C 240 4 Row 2...TDEBX11 2...1126 18...
3
/
16
2...C8
524A-B 300 3 Row 2...TDEBX11 2...1126 15...
1
/
4
2...C10
524A-C 300 4 Row 2...TDEBX11 2...1126 20...
3
/
16
2...C15
UNIT SIZE 524A 072 090 120 150 180 240 300
208/230-1-60
Speed (rpm) 1725 1725
Hp 1.3 2.4
Frame (NEMA) 56Y 56Y
ShaftDia(in.)
5
/
8
5
/
8
———
208/230-3-60 and 460-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1745 1745
Hp 2.4 2.4 2.4 2.9 3.7 5.0 7.5
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y S184T S213T
ShaftDia(in.)
5
/
8
5
/
8
5
/
8
7
/
8
7
/
8
1
1
/
8
1
3
/
8
575-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1745 1755
Hp 1.0 2.0 2.0 3.0 3.0 5.0 7.5
Frame (NEMA) 56 56HZ 56HZ 56HZ 56HZ 184T S213T
ShaftDia(in.)
5
/
8
7
/
8
7
/
8
7
/
8
7
/
8
1
1
/
8
1
3
/
8
50TFQ004-012
524A072-300

Other manuals for Bryant 566D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant 566D and is the answer not in the manual?

Bryant 566D Specifications

General IconGeneral
BrandBryant
Model566D
CategoryAir Conditioner
LanguageEnglish

Related product manuals