—24—
DETAILED COOLING CAPACITIES* Continued
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
†Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C).
** System kW is total of indoor and outdoor unit kilowatts.
†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.
EWB—Entering Wet Bulb
EVAP
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
650AN060-D, E Outdoor Section With FV4(A,B)NB006 Indoor Section
1750
72 70.1 35.6 4.43 66.6 34.4 4.92 63.1 33.1 5.47 59.2 31.7 6.07 55.0 30.3 6.73 50.2 28.7 7.42
67 64.4 45.5 4.35 61.3 44.2 4.85 58.0 42.9 5.40 54.5 41.5 6.00 50.6 40.0 6.65 46.4 38.4 7.35
63†† 60.2 44.3 4.30 57.2 43.0 4.79 54.2 41.7 5.34 50.9 40.3 5.94 47.3 38.8 6.60 43.4 37.1 7.30
62 59.2 55.1 4.29 56.4 53.7 4.78 53.5 52.3 5.33 50.5 50.4 5.93 47.5 47.5 6.60 44.2 44.2 7.32
57 57.8 57.8 4.27 55.6 55.6 4.77 53.1 53.1 5.32 50.5 50.5 5.93 47.5 47.5 6.60 44.2 44.2 7.32
2000
72 71.1 37.4 4.52 67.6 36.1 5.02 63.9 34.8 5.57 59.8 33.4 6.16 55.5 32.0 6.81 50.6 30.4 7.51
67 65.5 48.5 4.44 62.2 47.2 4.94 58.8 45.9 5.49 55.1 44.4 6.09 51.1 42.9 6.74 46.8 41.2 7.44
63†† 61.2 47.1 4.39 58.1 45.8 4.88 54.9 44.4 5.43 51.6 43.0 6.03 47.9 41.5 6.68 43.8 39.7 7.39
62 60.5 59.0 4.38 57.7 57.4 4.88 54.9 54.9 5.43 52.1 52.1 6.04 48.9 48.9 6.70 45.3 45.3 7.42
57 60.1 60.1 4.38 57.6 57.6 4.88 54.9 54.9 5.43 52.1 52.1 6.04 49.0 49.0 6.70 45.4 45.4 7.42
2250
72 72.0 39.1 4.61 68.3 37.8 5.10 64.4 36.5 5.65 60.4 35.1 6.25 55.9 33.7 6.90 50.8 32.0 7.59
67 66.2 51.4 4.53 62.9 50.1 5.03 59.4 48.7 5.57 55.6 47.3 6.17 51.7 45.7 6.83 47.1 43.9 7.53
63†† 61.9 49.8 4.48 58.8 48.5 4.97 55.6 47.1 5.52 52.1 45.6 6.12 48.3 44.0 6.77 44.1 42.1 7.48
62 61.8 61.8 4.48 59.2 59.2 4.98 56.5 56.5 5.53 53.5 53.5 6.14 50.2 50.2 6.80 46.4 46.4 7.51
57 61.8 61.8 4.48 59.2 59.2 4.98 56.4 56.4 5.53 53.4 53.4 6.14 50.2 50.2 6.80 46.4 46.4 7.51
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
CC5A/CD5AW 060 0.97 0.99
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CD5PX 060 0.97 1.02 CD5PX 060 0.97 1.00
CK5A/CK5BX 060 0.97 0.99
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
CK5PX 060 0.97 0.99 CC5A/CD5AW 060 0.97 0.98
FB4BNB 070 0.98 1.04
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
FC4CNB 070 0.98 1.04 CD5PX 060 0.96 1.04
FE4ANB 006 1.00 1.00
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
FK4DNB 006 1.00 1.00 CD5PX 060 0.97 1.03
FV4BNB 006 1.00 1.00
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
FX4BNB 060 0.98 1.04 CD5PX 060 0.95 1.00