EasyManua.ls Logo

Bryant 986TB - Cooling Mode Operation

Bryant 986TB
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
87
(1.) If the furnace control CPU selects lowheat opera-
tion the inducer motor IDM comes up to speed, the
lowheat pressure switch LPS closes, and the fur-
nace control CPU begins a 15sec prepurge period.
If the lowheat pressure switch LPS fails to remain
closed the inducer motor IDM will remain running
at highspeed. After the lowheat pressure switch
recloses the furnace control CPU will begin a
15sec prepurge period, and continue to run the
inducer motor IDM at highspeed.
(2.) If the furnace control CPU selects highheat opera-
tion, the inducer motor IDM remains running at
highspeed, and the highheat pressure switch re-
lay HPSR is deenergized to close the NC contact.
When sufficient pressure is available the highheat
pressure switch HPS closes, and the highheat gas
valve solenoid GVHI is energized. The furnace
control CPU begins a 15sec prepurge period after
the lowheat pressure switch LPS closes. If the
highheat pressure switch HPS fails to close and
the lowheat pressure switch LPS closes, the fur-
nace will operate at lowheat gas flow rate until the
highheat pressure switch closes for a maximum of
2 minutes after ignition.
b. Igniter WarmUp At the end of the prepurge period, the
HotSurface Igniter HSI is energized for a 17sec igniter
warmup period.
c. TrialForIgnition Sequence When the igniter warm
up period is completed the main gas valve relay contact
GVR closes to energize the gas valve solenoid GV
M. The
gas valve solenoid GVM permits gas flow to the burners
where it is ignited by the HSI. Five sec after the GVR
closes, a 2sec flame proving period begins. The HSI ig-
niter will remain energized until the flame is sensed or until
the 2sec flame proving period begins. If the furnace con-
trol CPU selects highheat operation, the highheat gas
valve solenoid GVHI is also energized.
d. FlameProving When the burner flame is proved at the
flameproving sensor electrode FSE, the inducer motor
IDM switches to lowspeed unless the furnace is operating
in highheat, and the furnace control CPU begins the
blowerON delay period and continues to hold the gas
valve GVM open. If the burner flame is not proved within
two sec, the control CPU will close the gas valve GVM,
and the control CPU will repeat the ignition sequence for
up to three more TrialsForIgnition before going to Igni-
tionLockout. Lockout will be reset automatically after
three hours, or by momentarily interrupting 115 vac power
to the furnace, or by interrupting 24 vac power at SEC1 or
SEC2 to the furnace control CPU (not at W/W1, G, R, etc.).
If flame is proved when flame should not be present, the
furnace control CPU will lock out of GasHeating mode
and operate the inducer motor IDM on high speed until
flame is no longer proved.
e. BlowerOn delay If the burner flame is proven the
blowerON delays for lowheat and highheat are as fol-
lows:
Lowheat 45 sec after the gas valve GVM is opened
the blower motor BLWM is turned ON at lowheat airflow.
Highheat 25 sec after the gas valve GV
M is opened
the BLWM is turned ON at highheat airflow. Simultan-
eously, the humidifier terminal HUM and electronic air
cleaner terminal EAC1 are energized and remain ener-
gized throughout the heating cycle.
f. Switching from Low to HighHeat If the furnace con-
trol CPU switches from lowheat to highheat, the furnace
control CPU will switch the inducer motor IDM speed
from low to high. The highheat pressure switch relay
HPSR is deenergized to close the NC contact. When suffi-
cient pressure is available the highheat pressure switch
HPS closes, and the highheat gas valve solenoid GVHI
is energized. The blower motor BLWM will transition to
highheat airflow five sec after the furnace control CPU
switches from lowheat to highheat.
g. Switching from High to LowHeat The furnace con-
trol CPU will not switch from highheat to lowheat while
the thermostat RtoW circuit is closed when using a
singlestage thermostat.
h. BlowerOff Delay When the thermostat is satisfied, the
R to W circuit is opened, deenergizing the gas valve GV
M, stopping gas flow to the burners, and deenergizing the
humidifier terminal HUM. The inducer motor IDM will re-
main energized for a 15sec postpurge period. The
blower motor BLWM and air cleaner terminal EAC1 will
remain energized at lowheat airflow or transition to low
heat airflow for 90, 120, 150, or 180 sec (depending on se-
lection at blowerOFF delay switches). The furnace con-
trol CPU is factoryset for a 120sec blowerOFF delay.
2. TwoStage Thermostat and TwoStage Heating
See Fig. 38 and 39 for thermostat connections.
NOTE: In this mode the lowheat only switch SW12 must be
ON to select the lowheat only operation mode in response to
closing the thermostat RtoW1 circuit. Closing the thermostat
Rto W1andW2 circuits always causes highheat operation,
regardless of the setting of the lowheat only switch.
The wall thermostat “calls for heat”, closing the RtoW1 circuit
for lowheat or closing the RtoW1andW2 circuits for
highheat. The furnace control performs a selfcheck, verifies the
lowheat and highheat pressure switch contacts LPS and HPS are
open, and starts the inducer motor IDM in highspeed.
The start up and shut down functions and delays described in item
1. above apply to the 2stage heating mode as well, except for
switching from low to highHeat and vice versa.
a. Switching from Low to HighHeat
If the thermostat
RtoW1 circuit is closed and the RtoW2 circuit closes,
the furnace control CPU will switch the inducer motor
IDM speed from low to high. The highheat pressure
switch relay HPSR is deenergized to close the NC contact.
When sufficient pressure is available the highheat pres-
sure switch HPS closes, and the highheat gas valve solen-
oid GVHI is energized. The blower motor BLWM will
transition to highheat airflow five sec after the RtoW2
circuit closes.
b. Switching from High to LowHeat If the thermostat
Rto W2 circuit opens, and the RtoW1 circuit remains
closed, the furnace control CPU will switch the inducer
motor IDM speed from high to low. The highheat pres-
sure switch relay HPSR is energized to open the NC contact
and deenergize the highheat gas valve solenoid GVHI.
When the inducer motor IDM reduces pressure suffi-
ciently, the highheat pressure switch HPS will open. The
gas valve solenoid GVM will remain energized as long
as the lowheat pressure switch LPS remains closed. The
blower motor BLWM will transition to lowheat airflow
five sec after the RtoW2 circuit opens.
3. Cooling mode
The thermostat “calls for cooling”.
a. SingleSpeed Cooling
See Fig. 38 and 39 for thermostat connections
The thermostat closes the R
toGandY circuits. The
Rto Y circuit starts the outdoor unit, and the Rto
GandY/Y2 circuits start the furnace blower motor
BLWM on cooling airflow. Cooling airflow is based on the
A/C selection shown in Fig. 64. The electronic air cleaner
986TB

Related product manuals