Vacation Setpoints
A special set of temperature setpoints exist which are active in vacation mode. They
are adjustable by the homeowner, are exclusively for vacation mode, and are
remembered from one vacation selection to the next. See Table 2 for default values.
Table 2 – Vacation Setpoints Default Values
MODE
AUTO
Fan Auto
Heat Setpoint 55_F/13_C
Cool Setpoint 85_F/29_C
OPERATIONAL INFORMATION
Timers
Five- Minute Compressor Timeguard
This timer prevents compressor from starting unless it has been off for at least 5
minutes. It can be overridden for 1 cycle by simultaneously pressing FAN and UP
buttons.
Cycle Timer
Based on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or 10
minutes. This much time must elapse from the start of one cycle before another
cycle can start. It serves to impose the cycles per hour limits. It can be defeated for
one cycle by simultaneously pressing the FAN and UP buttons.
Ten- Minute Staging Timer
In multistage heating or cooling, this timer prevents any higher stage from turning
on until preceding stage has been on for 1 0 minutes. When staging between
compressor and electric heat or between compressor and furnace heat, the time is
configurable. The timer is configurable via Option 17. This timer is overridden if