Operating Manual 37
Starting Up
10
Define the standard
for impedance.
This is needed so the
BVM will know
what abnormal
impedance looks
like.
NOTE: This section
sets the software and
controller to initial
mode. Do not
perform this if the
battery location is
not temperature-
controlled.
a. In the Location List, highlight a measurement that is close to the average of the values shown.
b. From the Communications window, click on Initial Impedance, then select Load Initial
Impedance Measurements to the Controller From BVM System Unit Settings.
c. From the menu bar, select Settings > Unit
Settings.
d. In the Software Unit Settings window, change
the Analysis Method from Average to Initial.
e. Click OK.
Action How to do it Picture