Logamatic SC40 - Technical specifications are subject to change without prior notice.
57
Service level menu (for qualified heating engineers only)
7
7.5.4 Collector maximum temperature
Menu: Service > Settings > Collector maximum temperature
If the collector maximum temperature is exceeded, the solar system pump is switched off or (if
already off) not switched on.
7.5.5 Evacuated tube collector function
Menu: Service > Settings > Tube collector function
In order to pump the heated solar solar fluid to the temperature sensor with evacuated tube collec-
tors, between the hours of 6:00 am and 10:00 pm and upwards of a collector temperature of 20 °C,
the solar system pump is switched on briefly every 15 minutes.
This function is not possible or is limited if the collector sensor is external to the collector.
Setting range Default setting New setting
100 - 140 °C 120 °C
Tab. 17
Setting range Default setting New setting
Yes/No No
Tab. 18
If the Tube collector function is active, the cooling function (Æ Section 7.5.22,
page 65) is automatically deactivated.

Other manuals for Buderus Logamatic SC40

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic SC40 and is the answer not in the manual?

Buderus Logamatic SC40 Specifications

General IconGeneral
BrandBuderus
ModelLogamatic SC40
CategoryNetwork Router
LanguageEnglish

Related product manuals