Particular safety instructions
BVS 16 ATEX E 118 X
DANGER!
To prevent the risk of explosion, observe not only the safety
instructions in the operating instructions for operation in the
potentially explosive atmosphere, but also the following:
Specicationsonthetypelabelconcerningtemperatureclass,
ambienttemperature,degreeofprotectionandvoltage.
Do not use device in areas where there is gas or dust with a
lower ignition temperature than indicated on the type label.
Installation,operationandmaintenancemaybeperformedby
qualiedtechniciansonly.
Observetheapplicablesafetyregulations(alsonationalsafety
regulations)aswellasthegeneralrulesoftechnologyforcon-
struction and operation.
Donotrepairthedeviceyourself,butreplaceitwithanequiva-
lentdevice.Repairsmaybeperformedbythemanufacturer
only.
Do not expose the device to any mechanical and/or thermal
loads which will exceed the limits described in the operating
instructions.
Use only cable and line entry points which have been approved
for the respective application area and which have been
screwed into place according to the associated installation
instructions.
Thecableglandsmaybeusedfortheinsertionofpermanently
installed cables and lines only.
Close all unnecessary cable glands with lock screws approved
forthepotentiallyexplosiveatmosphere.
Use pre-assembled cable glands according to the installa-
tioninstructionssuppliedbytheglandmanufacturer.Before
start-up in the potentially explosive atmosphere, check
whether the cable gland, as described in the associated
installation instructions, has been installed.
4.1 Special conditions of use
Do not use the device in dust atmospheres in which inten-
sive charging processes can be expected.
Usethedeviceonlyinanareawithatleastdegreeofsoil-
ing2,asdenedinIEC60994-1.
Ensure that the transient protection has been set to a value
whichdoesnotexceed140%ofthemeasuredpeakvoltage
valueatthesupplyconnectionsofthedevice.
Ifdevicesfeatureacircularplugconnection(multipole),the
mating plug will be provided by the end user and is not an
objectoftheapproval.Thematingplugmustsatisfythe
relevantrequirementsoftheIEC60079-0,IEC60079-7and
IEC60079-31andmusthaveatleasthousingdegreeof
protection IP65 according to IEC 60529.
Ifdevicesfeatureacircularplugconnection(multipole),use
aspeciallockingclipwhichpreventstheplugfrombeing
loosened without a tool.