AVW200-series 2-Channel Vibrating Wire Spectrum Analyzer Modules 
multi-dimensioned array of 5 or 6 if multiple sensors are 
being measured using a multiplexer. The first dimension is 
set equal to the number of sensors being measured and the 
second dimension is set equal to the number of values 
returned for each sensor (5 or 6).  For example, to measure 4 
sensors with thermistor measurements attached to a 
multiplexer, Dest would be declared as Array(4,6). Values 
for sensor 1 would be stored in Array(1,1) through 
Array(1,6), values for sensor 2 stored in Array (2,1) through 
(2,6), etc. 
  The values returned for each sensor are: 
 (1) Frequency in Hertz 
  (2)  Amplitude in mV RMS 
 (3) Signal-to-noise ratio 
 (4) Noise frequency 
 (5) Decay ratio 
  (6)  Thermistor in ohms (if measured) 
  The units and description of these values are provided in 
Table 2.1-2. 
  If communication is unsuccessful, NANs are stored.  
When using the CRBasic AVW200 instruction, the signal 
strength Amplitude in mV rms ( Dest(2) ) has a minimum 
resolution of 0.0625 (62.5 microvolts).  This means that values 
between 0.01 and 0.06249 mV (10 and 62.49 microvolts) will be 
given as 0.  Values between 0.0625 and 0.1249 will be given as 
0.0625.  Values between 0.125 and 0.18749 will be given as 
0.125, and so forth.  With firmware Std.04 and higher, values 
less than 0.01 will be shown as NAN, otherwise as 0. 
NOTE 
  To see amplitudes with higher resolution, use SDI-12 
(Section 3.3.1), Terminal mode (Section 5.7), or the 
"Troubleshoot" tab in DevConfig (Section 5.5) to examine 
signal strength amplitude values. 
AVWChan  The AVWChan is the channel on the AVW200 where the 
sensor or multiplexer is wired. Valid options are 1 (1V+/-) or 
2 (2V+/-).  
MuxChan  The MuxChan is the channel on the multiplexer where 
measurements should start. Valid options are 1 through 32; 
anything outside of this range returns an error.  Enter 1 if a 
multiplexer is not used.  
Reps  The Reps parameter is the number of measurements to be 
made on the multiplexer. This parameter does not affect the 
AVW200Chan.  
39