29
DRH
Modulation: Boiler Inlet, Boiler Fixed Setpoint Operation (Standalone)
• Boiler operates at a fixed
setpoint
• Modulates on boiler inlet
sensor (default)
• Heat demand is generated
when Remote Operator is
closed.
1) Place toggle switch to LOCAL
2) Press and
3) Press [CH – Central Heat Configuration]
4) Press the to arrive at Setpoint
5) Select Setpoint source: Local
6) Enter desired Setpoint
7) Place toggle switch to REMOTE for remote enable operation (if required)