EasyManua.ls Logo

Caple CR 9207 - Page 7

Caple CR 9207
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
Electrical feeder cable
connection
To connect the feeder cable to the cooker
it is necessary to:
Remove the screw that hold shield “A
behind the cooker (fig. 1.2).
Insert the feeder cable of the suitable
section (as described in the next
chapter) into the cable clamp “D”.
Connect the phase and earth cables
to the terminal block “B” according to
the diagram in figure 1.3.
– Pull the feeder cable and block it with
cable clamp “D”.
Re-mount shield “A”.
N.B. The earth conductor must be left
about 3 cm longer than the others.
Fig. 1.2
D
B
A
230 V
PEN
L
1
(L2)
Fig. 1.3
PE
Electrical Installation - Wall box connection
FEEDER CABLE SECTION
type H05RR-F
230 V 3 x 2,5 mm
2
(**)
(**) – Connection with wall box connection.
PE Earth
N Neutral
L Live
This appliance must be connected to a
double pole isolating switch (fig. 1.1) and
to the terminal block in the cooker (figs.
1.2, & 1.3) using the following guide:
FUSE
DOUBLE POLE SWITCHED
FUSED SPUR OUTLET
USE A 20 AMP FUSE
ON
Fig. 1.1
1) The wire which is coloured brown
must be connected to the terminal
marked L (Live), or coloured Red.
2) The wire which is coloured blue must
be connected to the terminal marked
N (Neutral), or coloured Black.
3) The wire which is coloured green
and yellow must be connected to
the terminal marked E (Earth)
or coloured Green.
IMPORTANT: These connections must
be carried out by a qualified electrical
engineer.

Related product manuals