19Heosone +050002740 rel. 1.1 - 17.05.2021 Installation
ENG
3.5 Electrical installation
Caution:
before carrying out any maintenance, disconnect the controller from the power supply by moving the main system switch
to off. Once having powered down the controller, wait at least 5 minutes before disconnecting the electrical cables;
always make sure that the compressor has stopped completely. Freely rotating motors may generate dangerous voltages
across the terminals on Heosone, even when this is not powered;
the controller does not feature protection against short-circuits to earth; suitable devices must be used to detect faults
upstream of the circuit.
Description of the terminals
50002730_014_R01
7
6 5 4 3 12
U V W L N
J13
C3 NO3
J2 J1
J7
J6 J5 J4 J3
J10J11
J12
C1/ 2 NO2 NO1
J9
J8
J14
11
14
10
13 12
8
9
Fig. 3.m
Ref. Connector Description
1 J1 L, N Single-phase power supply (see the Technical specifications)
Earth (*)
2
Earth (*)
U, V, W Compressor output
3 J3 (**) Evaporator fan
4 J4 (**) Condenser fan
50002730_019_R01
1234567
J3 / J4
1Vdc
2 Reserved
3 Reserved
4 GND
5Vdc
6 VSP - set point output
7 FG - tachometer input
5 J5 Reserved
6 J6 Safety digital input (Safety Torque Off (***))
7 J7 Fieldbus
8 J8 User terminal connector
9 J9 BMS connector