5.1 Connector table
Ref. Wiring terminals
Wire cross- sec-
tion (mm
2
)
Lmax
(m)
J1 Spade: 6.3 mm female 1.5 -
Spade: 6.3 mm female 1.5 -
Spade: 6.3 mm female 1.5 -
J2 Lumberg 3575 03 …, MOLEX 91627-1502, TE 1-1740533-3 0.75 3
J3 JST XHP-7 0.3 3
J4 JST XHP-7 0.3 3
J5 Not used --
J6 Lumberg 3575 02 k10 Stocko 7262-002-004-960-000-00-g
J7 Lumberg 3612 03…, Sauro CUF03001, Weco 130-P-020/3 0.13 10
J8 JST XHP-4 connector (user terminal side: JST ZHR-4 pin) +SXH-002T-P0.6 (terminal) 0.13 10
J9 Degson 15EDGK-3.81-03P-14-00A(H), Phoenix Contact MC 1.5/3-ST-3.81 0.081 to 1.31 500
J10 MOLEX Micro- FIT 43025- 0800, FCI Minitek 0430300004, FCI10127718-002PLF
(terminal) 10127716-08LF (connector) + Molex
0.05 to 0.52 10
J11 MOLEX Micro- FIT 43025- 1000, FCI Minitek 0430300004, FCI10127718-002PLF
(terminal) 10127716-10LF (connector) + Molex
0.05 to 0.52 10
J12 DEGSON 2EDGK-5.08-03P-14-13A(H)M3, PHOENIX CONTACT MSTB 2.5/3-ST-5.08, SAURO CIF03005 0.21 to 2.5 10
J13 DEGSON 2EDGK-5.08-02P-14-13A(H)M3, PHOENIX CONTACT MSTB 2.5/2-ST-5,08, SAURO CIF02005 0.21 to 2.5 10
J14 CAREL EXV unipolar valve connector Pre-wired
Tab. 5.c
5.2 Rated current values
The following table shows the rated input current and output current values, as well as the specifications for sizing the cables
(cross-section, maximum length) and the fuses.
Model
Rated input
current
Protection
fuses (*)
Protection
fuses for USA -
CAN (**)
Rated output
current
Power cable
size
Minimum
compressor
cable size
Maximum
compressor
cable length
(A) (A) (A) (A) (mm
2
) (mm
2
) (m)
all versions
115 Vac / Small
3.8 16 15 1.3 1.5 0.75 3
all versions
230 Vac / Small
2 16 15 1.3 1.5 0.75 3
all versions
230 Vac / Medium
3.8 16 15 2.6 1.5 0.75 3
Tab. 5.d
(*) type gG;
(**) type CC