10. TECHNICAL SPECIFICATIONS AND SOFTWARE UPDATES
10.1 Technical specifications
Electrical specifications
In the following specifications “Group A” defines the grouping of the following outputs: valve, pump,
compressor, heater.
Power supply 24 Vac, range +10/–15 %; 50/60 Hz
Maximum power input: 3W
Fuse (compulsory) in series with the power supply to the µC
2
: 315mAT
12 pin connector Max. current 2 A for each relay output, extendable to 3 A for one single output
Relays Max current at 250 Vac: EN60730: resistive: 3A, Inductive: 2A cosj =0.4 60,000
cycles
UL: Resistive: 3A, 1 FLA, 6 LRA cos
j =0.4 30,000 cycles
For further information refer to the characteristics shown in Figure 10.a
Minimum interval between communications (each relay): 12 s (the manufacturer
of the unit that the device is integrated into must ensure the correct configuration
so as to respond to this specification
Type of microswitching: 1 C
Insulation between relays in group A: functional
Insulation between the relays in group A and the very low voltage parts:
reinforced
Insulation between relays in group A and the signal relays: primary
Insulation between the signal relays and the very low voltage parts: reinforced
Insulation between the relays and the front panel: reinforced
Digital inputs Electrical standard: voltage-free contacts
Closing current to earth: 5 mA
Maximum closing resistance: 50 W
Analogue inputs B1, B2, B3, B4: NTC CAREL temperature probes (10 kW at 25 °C)
The response time depends on the component used, typical value 90 s
B4: NTC temp. probes (10 kW at 25 °C) or CAREL 0 to 5 V ratiometric pressure
probes SPKT00**R*
Fan output
Control signal for CAREL modules MCHRTF****, CONVONOFF* and
CONV0/10A*
Phase width modulation (settable width) or modulation of the duty cycle
No-load voltage: 5V ± 10%
Short-circuit current: 30 mA
Minimum output load: 1 kW
Front panel index of protection Panel mounting version IP55, DIN-rail version IP40
Storage conditions -10T70 °C – humidity 80 % rH non-condensing
Operating conditions -10T55 °C – humidity <90 % rH non-condensing
Degree of pollution Normal
Cat. of resist. to heat and fire D (RU94 V0)
PTI of the insulating materials All the insulating materials have PTI≥250 V
Software class and structure A
Period of electric stress across
insulating parts
Long
Homologations CE/RU (File EI98839 sez.16)
Table10.a
Note: all the relays must have the common terminals (C1/2, C3/4, C6/7, C8/9) connected together.
Functional characteristics
Resolution of the analogue inputs Temperature probes: range -40T80 °C, 0.1 °C
Temperature measurement error Range -20T20 °C, ±0.5 °C (excluding probe)
Range -40T80 °C, ±1.5 °C (excluding probe)
Pressure measurement error The % error with a voltage reading with a range of input from 0.5 to 4.5
is ± 2% (excluding probe).
The error in the converted value may vary according to the settings of
parameters /9, /10, /11, /12
Table 10.b
Characteristics of the connectors
The connectors may be purchased using CAREL code (MCHCON0***) or from the manufacturer Molex
®
Molex
®
codes of the connector Number of pins
39-01-2120 12
39-01-2140
14
Table 10.c
Max. number of insertion/removal cycles for the connectors: 25 cycles
Code of the contacts according to the cross-section of the connection cables to the 12- and 14-pin con-
nectors (use the special Molex
®
tool code 69008-0724 for crimping
Molex
®
code of the contact Cross-section of cables allowed
39-00-0077 AWG16 (1,308 mm
2
)
39-00-0038 AWG18-24 (0,823...0,205 mm
2
)
39-00-0046 AWG22-28 (0,324...0,081 mm
2
)
Table 10.d
In addition, the pre-wired kits MCHSMLC*** are also available
numero di operazioni (x 10
4
)
corrente sui contatti (A)
Fig. 10.a