EasyManuals Logo

Carlyle TS Series User Manual

Carlyle TS Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
10
1.1 Refrigerants and Lubricants
Approved Refrigerants
The Paragon medium-temperature screw compressor is
specifically designed for use in R-134a systems.
Approved Lubricants
The Paragon screw compressor is approved for use with
the following lubricants:
Approved Lubricant — Emkarate RL 220H
Viscosity Grade — ISO 220
or
Approved Lubricant — Emkarate RL 220HC
Viscosity Grade — ISO 220
Carrier Part Number — 1 gallon: P903-2301
5 gallon: P903-2305
Assembly Grease
On occasion, it may be necessary to use an assembly
grease to retain an o-ring within its groove. The follo
wing
assembly grease is approved for use with the Paragon
screw compressor:
Approved Lubricant — Castrol Synplex GP2
or
Approved Lubricant — Parker Super-O-Lube
Carrier Part Number — 19XL680001
Terminal Pin Dielectric Grease
Carlyle recommends that compressor motor terminal
pins are coated with dielectric grease (P/N 06TT660050)
to reduce the effects of condensation that may form on
the terminal pins.
1.2 Environmental Considerations
Operating Ambient Temperature
The screw compressor is designed for the following ambi-
ent temperature ranges:
Non-Operating: -40°F to 176°F (-40°C to 80°C)
Operating: -31°F to 131°F (-35°C to 55°C)
Salt-Spray Requirements
The compressor has been tested through 500 hours of
salt-spray in compliance with ASTM specification B-117.
1.3 Operating Limits and Controls
R-134a, R-513A, R-1234ze Operating Envelope
The following operating envelopes show where the com-
pressor can be operated in both direct expansion and
flooded applications. See Fig. 5-
7. The envelopes differ
for the unique design configuration of the compressor.
The fifth digit of the model number indicates the operat-
ing envelope. The load line percentages refer to the
capacity relative to full load at the same saturated suction
temperature (SST) and saturated discharge temperature
(SDT).
1.0 Medium/High Temperature System Design
Considerations (R-134a, R-513A, R-1234ze)