4-4-3. Typical indication flow
Data can be displayed in real time. Operation time, on-off times, temperature, set value, 
alarm informations etc are displayed. Each data is identified by the data code.
You can scroll the data code by ▲▼ key.  It shows an alarm code only when an abnormality occur
and when multiple abnormality occurrs the highest-priority one is displyed and a dot is shown 
at the bottom right of the alam code.
The remaining alame code can be shown with ▲▼ key.
 When there is no key operation for 1 minute or "Back" key is pressed, the display returns to
generator temperature indication.
Typical indication flow
*1 It will display flick at the time of remote setting
*2 It may not display depending on the specification
Data code
Data name Display Meaning
- Genarator temperature
135.0 
o
C (
o
F)
1. Chiller operation hours
1234hours
2. #1 absorbent pump operation hours
1111hours
3. #2 absorbent pump operation hours
1230hours
4. -
not used
5. -
not used
6. Refrigerant pump operation hours
1201hours
7. Purge pump operation hours
107hours
8. -
not used
9. Combustion hours
not used
A. Chiller on/off times
123times
B. #1 absorbent pump on/off times
169times
C. #2 absorbent pump on/off times
123times
D. -
not used
E. -
not used
F. Refrigerant pump on/off times
138times
G. Purge pump on/off times
51times
H. -
not used
I. Combustion on/off times
not used
10. Chilled water temperature setting point *1
7.0 
o
C (
o
F)
11. Hot water temperature setting point
not used
12. Chilled water inlet temperature
11.9 
o
C (
o
F)
13. Chilled water outlet temperature
6.8 
o
C (
o
F)
14. -
not used
15. -
not used
16. Cooling water inlet temperature
31.8 
o
C (
o
F)
17. Driving hot water inlet temperature *2
90.0 
o
C (
o
F)
18. Hot water control valve retern temperature
option
19. Condenser temperature
34.7 
o
C (
o
F)
20.
Driving hot water outlet / steam drain / exhaust gas temperature
80.0 
o
C (
o
F)
21. Purge tank pressure
8.5kPa
- Generator temperature
135.0 
o
C (
o
F)
4-7