4-4-3. Typical indication flow
Data can be displayed in real time. Operation time, on-off times, temperature, set value,
alarm informations etc are displayed. Each data is identified by the data code.
You can scroll the data code by ▲▼ key. It shows an alarm code only when an abnormality occur
and when multiple abnormality occurrs the highest-priority one is displyed and a dot is shown
at the bottom right of the alam code.
The remaining alame code can be shown with ▲▼ key.
When there is no key operation for 1 minute or "Back" key is pressed, the display returns to
generator temperature indication.
Typical indication flow
*1 It will display flick at the time of remote setting
*2 It may not display depending on the specification
Data code
Data name Display Meaning
- Genarator temperature

135.0
o
C (
o
F)
1. Chiller operation hours

1234hours
2. #1 absorbent pump operation hours

1111hours
3. #2 absorbent pump operation hours

1230hours
4. -

not used
5. -

not used
6. Refrigerant pump operation hours

1201hours
7. Purge pump operation hours

107hours
8. -

not used
9. Combustion hours

not used
A. Chiller on/off times

123times
B. #1 absorbent pump on/off times

169times
C. #2 absorbent pump on/off times

123times
D. -

not used
E. -

not used
F. Refrigerant pump on/off times

138times
G. Purge pump on/off times

51times
H. -

not used
I. Combustion on/off times

not used
10. Chilled water temperature setting point *1

7.0
o
C (
o
F)
11. Hot water temperature setting point

not used
12. Chilled water inlet temperature

11.9
o
C (
o
F)
13. Chilled water outlet temperature

6.8
o
C (
o
F)
14. -

not used
15. -

not used
16. Cooling water inlet temperature

31.8
o
C (
o
F)
17. Driving hot water inlet temperature *2

90.0
o
C (
o
F)
18. Hot water control valve retern temperature

option
19. Condenser temperature

34.7
o
C (
o
F)
20.
Driving hot water outlet / steam drain / exhaust gas temperature

80.0
o
C (
o
F)
21. Purge tank pressure

8.5kPa
- Generator temperature

135.0
o
C (
o
F)
4-7