4-5. HOW TO CHANGE THE INDICATION AND THE SETTING POINT
4-5-1. Indication of setting
The present "chilled water temperature setting", or "Hot water temperature setting" can be checked
by following Section 4-4-2. How to change the indication.
4-5-2. How to change setting
After showing present setting, it can be changed in the following process.
To change the temperature
of chilled water setting

7.0
Press the"SET"key
for about 2 seconds.

A numeral that shows setting
point temperature blinks.
Press""or"" key.

7.5
Press the"SET"key

Setting is changed.
When there is no key operation for 1 minute or "BACK" key is pressed, the display returns to
generator temperature indication.
NOTE 1: Wrong setting may cause a failure of the Chiller.
If you need to change setting, be sure to contuct service agent
NOTE 2: The changed setting become instantly effective upon changing it.
Be careful in changing the set values during operation.
4-8