5-7
4. Discharge the water from the discharge port on the cooling water inlet.
5. Keep the discharge port open during shut down.
(2) Chilled water
Keep the evaporator full with the water. (Wet lay up)
(3) Hot water
Keep the generator full with the water. (Wet lay up)
5-3-3. Winter season
In case the ambient temperature of the Chiller is likely to be below 0, freeze protection is
necessary.
Consult the service agent for details.
5-4. RECOMMENDED SCHEDULE FOR MAINTENANCE
AND REPLACEMENT OF MAIN COMPONENTS
Parts
division
Name of Parts Replacement timing Replacement cycle
Water
line
Gasket of water line After opening
Partition plate of water box If necessary
Heat transfer tubes Based on inspection result
Body parts
Heat exchanger If necessary
Absorbent ,Refrigerant Based on inspection result
Refrigerant pan If necessary
Service valve spindle Periodic replacement 6 years
Sight glass & packing Periodic replacement 6 years
Diaphragm packing Periodic replacement 6 years
Diaphragm valve If necessary
Palladium cell Periodic replacement 3 years
Palladium cell heater Periodic replacement 3 years
Rupture disc Periodic replacement annual
Angle valve If necessary
Check valve If necessary
Damper If necessary
Purge unit (ejector unit) Periodic replacement 8 years
Pump
Absorbent pump (#1 / #2) Periodic replacement 10 years / 20,000h
Refrigerant pump Periodic replacement 10 years / 20,000h
Purge pump If necessary
Control devices
Inverter(option) Periodic replacement 5 years
Fan for inverter(option) Periodic replacement 3 years
Reactor for inverter(option) If necessary
Electromagnetic contactor Periodic replacement 5 years
Circuit breaker If necessary
CPU, indicator, IO, power board Periodic replacement 7 years
Control relay Periodic replacement 5 years
Timer Periodic replacement 5 years
Cooling fan Periodic replacement 5 years
Generator temp. sensor If necessary
Temp. sensor If necessary
Pressure sensor Periodic replacement 5 years
Flow switch Periodic replacement 8 years
Transformer If necessary
These replacement cycle have been assumed in consideration of performing a periodic maintenance.