4-7-3. Content of alarm and setting
List of alarm and setting
Purpose Display Contents of alarm Set point
Chilled water

Chilled water temperature is too low. 2.5
o
C(36.5
o
F) or below
freeze protection

Chilled water pump interlock failure
-

Few flow rate of chilled water
50% or below

Cooling water temperature is too low. 24
o
C(75.2
o
F) or below
continues 30 minutes

Cooling water pump operation failure.
-

Refrigerant temperature is too low. 2.0
o
C(35.6
o
F) or below
Crystallization

Cooling water pump interlock failure
-
prevention

Few flow rate of cooling water(option)
50% or below

Generator’s temperature is too high. 105
o
C(221
o
F) or avove
Protection of

High concentration of absorbent
2 times of 65.0%
generator
or above
65.5% or above
Motor protection

No.1 Absorbent pump is overloaded.
Rated current

No.2 Absorbent pump is overloaded.
value or above

Refrigerant pump is overloaded.

Purge pump is overloaded.
Others

Chilled water flow switch failure
-

Cooling cycle failure
*1

Power failure (while operating)
More than 1 hour
*1 Chilled water temp. difference 1.0
o
C(1.8
o
F) or below for 30min. at 85% or above input.