15
180 200 220 300 330 400 430 470 520
Sound power
(3)
dB(A) 91 92 92 92 92 93 93 93 93 94 94 94
Sound pressure at 10 m
(4)
dB(A) 59 60 60 60 60 60 60 61 61 62 62 62
(1)
Sound power
(3)
dB(A) 89 90 90 90 90 91 91 92 92 93 93 93
Sound pressure at 10 m
(4)
dB(A) 57 58 58 58 58 59 59 60 60 61 61 61
(1)
Sound power
(3)
dB(A) 85 85 85 86 86 86 86 87 87 88 88 88
Sound pressure at 10 m
(4)
dB(A) 53 53 53 54 54 54 54 55 55 55 55 56
Length mm 2410 3604 4797
Width mm 2253 2253 2253
Height mm 2297 2297 2297
(2)
Standard unit kg 1216 1257 1257 1387 1408 1865 1901 2069 2125 2545 2563 2761
Standard unit + option 15
(1)
kg 1299 1339 1340 1495 1516 1991 2027 2212 2269 2707 2726 2941
Standard unit + option 15 + option 116S
(1)
kg 1438 1479 1479 1634 1670 2151 2231 2416 2472 2950 2967 3221
Hermetic Scroll 48.3 rps
Circuit A 1 1 1 2 2 2 2 3 3 3 3 4
Circuit B 2 2 2 2 2 3 3 3 3 4 4 4
No. of power stages 3 3 3 4 4 5 5 6 6 7 7 8
(2)
R410A
Circuit A kg 8,40 10,90 10,90 12,60 13,10 14,70 15,40 20,30 21,10 23,50 23,50 26,75
tCO
2
e 17,5 22,8 22,8 26,3 27,4 30,7 32,2 42,4 44,1 49,1 49,1 55,9
Circuit B kg 12,25 12,60 12,60 12,70 13,10 20,20 20,20 20,40 22,20 26,70 26,80 26,95
tCO
2
e 25,6 26,3 26,3 26,5 27,4 42,2 42,2 42,6 46,4 55,7 56,0 56,3
Pro-Dialog+ Control
Minimum capacity % 33% 33% 33% 25% 25% 20% 20% 17% 17% 14% 14% 13%
Aluminium micro-channel coils (MCHE)
Axial Flying Bird 4 fans with rotating shroud
Quantity 3 4 4 4 4 5 5 6 6 7 7 8
Maximum total air ow l/s 13542 18056 18056 18056 18056 22569 22569 27083 27083 31597 31597 36111
Maximum rotational speed rps 16 16 16 16 16 16 16 16 16 16 16 16
Dual-circuit plate heat exchanger
Water content l 15 15 15 15 19 27 35 33 42 44 47 53
Max. water-side operating pressure without
hydronic module
kPa 3200 3200 3200 3200 3200 3200 3200 3200 3200 3200 3200 3200
Pump, Victaulic screen lter, safety relief valve, water and air drain valve, pressure sensors, expansion tank
(option)
Pump Centrifugal pump, monocell, 48.3 rps, low or high pressure (as required), single or dual (as required)
Expansion vessel volume l 50 50 50 50 50 80 80 80 80 80 80 80
Max. water-side operating pressure with
hydronic module
kPa 400 400 400 400 400 400 400 400 400 400 400 400
Victaulic
®
type
Connections inches 3 3 3 3 3 4 4 4 4 4 4 4
External diameter mm 88,9 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3 114,3 114,3 114,3
Colour code RAL 7035
(1) Options: 15 = low noise level, 15LS = very low noise level, 116S = High-pressure dual-pump hydronic module.
(2) Values are guidelines only. Refer to the unit name plate.
(3)
in dB ref=10
-12
W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in accordance with ISO 9614-1 and
certied by Eurovent.
(4) In dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information, calculated from the sound power
Lw(A).