18
The pumps tted to these units have motors which meet efciency class IE2 for motors < 7.5kW and IE3 for motors > 7.5kW.
The additional electrical data required
(1)
is as follows:
For the low-pressure single pump motors of 30RBM/RBP 160-520 units (option 116T)
(2)
(3)
180 200 220 300 330 400 430 470 520
1 Nominal eciency at full load and nominal voltage % 85,7 85,7 85,7 85,7 85,7 87,5 87,5 87,5 89,9 89,9 89,9 89
1 Nominal eciency at 75% of full load and nominal voltage % 86,9 86,9 86,9 86,9 86,9 88,2 88,2 88,2 90,4 90,4 90,4 90
1 Nominal eciency at 50% of full load and nominal voltage % 86,4 86,4 86,4 86,4 86,4 87,5 87,5 87,5 89,6 89,6 89,6 89,7
2 Eciency level - IE3
3 Year of manufacture - This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4 Company name or trademark, commercial registration number and
head oce of manufacturer
- Same as above
5 Product model number - Same as above
6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 2
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 2,2 2,2 2,2 2,2 2,2 3 3 3 4 4 4 5,5
7-2 Maximum input power (400 V)
(4)
kW 2,80 2,80 2,80 2,80 2,80 3,81 3,81 3,81 4,96 4,96 4,96 6,80
8 Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 X 400
9-2 Maximum current drawn (400 V)
(5)
A 4,92 4,92 4,92 4,92 4,92 6,81 6,81 6,81 8,27 8,27 8,27 11,30
10 Nominal speed rps - rpm 48 - 2900
11 Product disassembly, recycling or disposal at end of life - Disassembly using standard tools. Disposal and recycling using an appropriate company.
12 Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000
(6)
II - Ambient air temperature °C < 40
IV - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in the specic
conditions in the Carrier selection programs.
V - Potentially explosive atmospheres - Non ATEX environment
(1) Required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydronic module, add the maximum unit current draw from the electrical data table to the pump current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
For the low-pressure dual pump motors of 30RBM/RBP 160-520 units (option 116T)
(2)
(3)
180 200 220 300 330 400 430 470 520
1 Nominal eciency at full load and nominal voltage % 84,9 84,9 85,7 85,7 87,5 87,5 87,5 87,5 89,9 89,9 89,9 89
1 Nominal eciency at 75% of full load and nominal voltage % 86,4 86,4 86,9 86,9 88,2 88,2 88,2 88,2 90,4 90,4 90,4 90
1 Nominal eciency at 50% of full load and nominal voltage % 85,9 85,9 86,4 86,4 87,5 87,5 87,5 87,5 89,6 89,6 89,6 89,7
2 Eciency level - IE3
3 Year of manufacture - This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4 Company name or trademark, commercial registration number and
head oce of manufacturer
- Same as above
5 Product model number - Same as above
6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 2
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 1,5 1,5 2,2 2,2 3 3 3 3 4 4 4 5,5
7-2 Maximum input power (400 V)
(4)
kW 1,94 1,94 2,80 2,80 3,81 3,81 3,81 3,81 4,96 4,96 4,96 6,80
8 Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 X 400
9-2 Maximum current drawn (400 V)
(5)
A 3,41 3,41 4,92 4,92 6,81 6,81 6,81 6,81 8,27 8,27 8,27 11,30
10 Nominal speed rps - rpm 48 - 2900
11 Product disassembly, recycling or disposal at end of life - Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12 Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000(6)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in the specic
conditions in the Carrier selection programs.
V - Potentially explosive atmospheres - Non ATEX environment
(1) Required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydronic module, add the maximum unit current draw from the electrical data table to the pump current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.