35


The system ow rate is not set at a nominal value.
The ow rate will be adjusted, by varying the pump speed, to
maintain a heat exchanger temperature differential value
dened by the user.
This is checked by the temperature sensors at the water
exchanger inlet and outlet (items 8 and 9 on the main water
circuit diagram).
The system reads the measured temperature values, calculates
the corresponding temperature delta, compares it with the
setpoint value set by the user and then modulates the pump
speed module.
This results in an increase in the flow rate if the
temperature delta exceeds the setpoint.
This results in a decrease in the ow rate if the temperature
delta is less than the setpoint.
This modulation is limited only by the maximum and minimum
ow rates for the unit and by the maximum and minimum
allowable pump speeds.
The maintained temperature delta may, in certain cases, differ
from the setpoint value:
if the setpoint value is too high (obtained for a ow rate
lower than the minimum value or a frequency less than
the minimum value), the system will stop once it reaches
the minimum ow rate or minimum frequency, which will
result in a temperature delta below the setpoint,
if the setpoint value is too low (obtained for a ow rate
higher than the maximum value or a frequency greater
than the maximum value), the system will stop once it
reaches the maximum ow rate or maximum frequency,
which will result in a temperature delta above the setpoint.
Contact the manufacturer's service department to implement
the procedures described below.
Hydronic circuit cleaning procedure
Refer to the hydronic circuit cleaning procedure.
Procedure for controlling the temperature delta setpoint
Once the circuit is cleaned, stop the forced start of the pump
and proceed to the conguration of the unit for the required
control mode.
Modify the control parameters:
Water ow rate control method (temperature differential)
Set the value of the required differential temperature.
The unit's default factory conguration is the minimum speed
(frequency: 30 Hz).


The ow will be set to a nominal value. This value will remain
constant and will not be dependent on variations in the
system's load.
Contact the manufacturer's service department to implement
the procedures described below
Hydronic circuit cleaning procedure
Refer to the hydronic circuit cleaning procedure.
Procedure for controlling the ow rate
Once the circuit has been cleaned, set the required water ow
rate by adjusting the pump frequency on the user interface.
Stop the forced operation of the pump and proceed to the
conguration of the unit for the required control mode. Modify
the control parameters:
Water ow rate control method (xed speed)
Constant frequency value.
The unit's default factory conguration is the minimum speed
(frequency: 30 Hz).