Carrier 30XA - Configuration Menu Options and Settings

Carrier 30XA
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
6.4 - 
Icon Displayed text* Description Associated table
General Conguration General conguration GEN_CONF
Pump Conguration Pump conguration PUMPCONF
User Conguration User conguration USERCONF
Reset Conguration Reset conguration RESETCFG
Schedule Menu Schedule menu SCHEDULE
Holiday Menu Holiday menu HOLIDAY
Broadcast Menu Broadcast menu BROCASTS
Date/Time Conguration Date/time conguration DATETIME
Control Identication Control identication CTRL_ID
*Depends on the selected language (English by default).

No. Status Default Unit Displayed text* Description
1 0 to 2 0 - Cir Priority Sequence Circuit priority
2 0=Auto, 1=A Prio 0 = Automatic circuit selection
1 = Circuit A priority
3 2=B Prio 2 = Circuit B priority
4 no/yes no - Staged Loading Sequence Staged loading sequence
5 no/yes no - Ramp Loading Select Ramp loading selection
6 1 to 15 1 min Unit O to On Delay Unit O to On delay
7 00:00 0 - Night Mode Start Hour Night mode start time
8 00:00 0 - Night Mode End Hour Night mode end time
9 0 to 100 100 % Night Capacity Limit Night capacity limit
10 Basic Menu Conguration Basic menu conguration
11 0 = All Access 0 = All access
12 1 = no alarm menu 1 = No alarm menu
13 2 = no setpoint menu 2 = No setpoint menu
14 3 = 1 + 2 3 = No alarm and no setpoint menu
15 0 to 2 0 - Demand Limit Type Select Demand limit selection
16 0 = None 0 = None
17 1 = Switch Control 1 = Switch control
18 2 = 4-20mA Control 2 = 4-20 mA control
19 0 to 20 0 mA mA For 100% Demand Limit 100% demand Limit (mA)
20 0 to 20 10 mA mA For 0% Demand Limit 0% demand Limit (mA)
21 no/yes no - Current Limit Select Current limit selection
22 0 to 4000 2000 A CurrentLimit at 100% Current limit at 100%
23 14.4 to 15 10 ^C Free Cooling Delta T Th Free cooling delta temperature
24 20 to 300 30 min Full Load Timeout Full load timeout
25
no/yes no - Ice Mode Enable Ice mode enabled
26 no/yes no - Reverse Alarms Relay Reverse alarms relay
*Depends on the selected language (English by default).