7.5 - Heating/Cooling selection
selection can be controlled in various ways, depending on the
active operating type. By default, the cooling mode is selected.
Heating/cooling control can be automatic or manual.
Heating/Cooling selection can be determined as follows:
• locally at the unit in the GENUNIT menu,
• remotely via the heating/cooling selection contact if
the unit is in the Remote operating type,
• via a network command if the unit is in the Network
operating type.
In the automatic mode, the outdoor air temperature
determines the heating/cooling/standby changeover (see the
SETPOINT menu for cooling and heating mode changeover
thresholds). The automatic changeover is optional and requires
Parameter status
status
Control
type
Heating/Cooling
selection in local
mode
Heating/Cooling
contact in local
mode
Heat/Cool
select
Operating
mode
o - - - cooling
on local cooling - cooling
on local heating - heating
on remote - on cooling cooling
on remote - on heating heating
on network - - cooling cooling
on network - - heating heating
NOTE: Please remember that the automatic changeover
mode cannot be selected on water-cooled units.
7.3 - Pumps control
The main control can manage one or two water exchanger
pumps, determining each pump on/off state. Both pumps
cannot run together. The pump is turned on when this option
The pump is turned off when the unit is shut down due to an
alarm unless the fault is a frost protection error. The pump
can be started in particular operating conditions when the
water exchanger heater is active.
If the pump has failed and another pump is available, the
unit is stopped and started again with the second pump. If
there is no pump available, the unit shuts down.
Water
ow switch in section 3.8.
7.3.1 - Pumps conguration
Basic pump configuration can be performed via the
Only logged-in users can access the menu (see also section
4.3.3). The unit must be stopped.
For units with two pumps, these pumps can be controlled
automatically or each pump can be started manually.
7.3.2 - Automatic pump selection
If two pumps are controlled and the reversing function has
pump changeover delay. If this delay has elapsed, the pump
reversing function is activated.
7.3.3 - Pumps protection
The control provides the option to automatically start the
pump each day at 14:00 for 2 seconds when the unit is off.
The heater for the heat exchanger and the water pump (for
units with a pump) can be energised so that it protects the
heat exchanger or the water pump against any damage when
the unit is shut down for a long time at low outdoor temperature.
on even days and the second pump is started on odd days.
Starting the pump periodically for a few seconds extends the
lifetime of the pump bearings and the tightness of the pump
seal. Periodical pump quick start can be selected via the
Pump Sticking Protection, PUMPCONF
7.4 - Condenser water pump control
The water condenser pump control applies to air-cooled units
cooled units. This function ensures constant water pumps
and operating cost savings.