COMMUNICATION FAILURE
54 4101 Communication loss with Compressor Board A Automatic, if
communication is
re-established
Unit shuts down Bus installation fault or
defective board
55 4201 Communication loss with Compressor Board B As above Unit shuts down As above
56 4301 Communication loss with Compressor Board C As above Unit shuts down As above
57 4901 Communication loss with SIOB Board Number 1 As above Unit shuts down As above
58 4902 Communication loss with SIOB Board Number 2 As above Unit shuts down As above
59 4903 Communication loss with SIOB Board Number 3 As above Unit shuts down As above
60 4904 Communication loss with SIOB Board Number 4 As above Unit shuts down As above
61 4905 Communication loss with SIOB Board Number 5 As above Unit shuts down As above
62 4906 Communication loss with SIOB Board Number 6 As above Unit shuts down As above
63 4501 Communication loss with Fan Board Number 1 As above Circuit A shuts down As above
64 4502 Communication loss with Fan Board Number 2 As above Circuit B shuts down As above
65 4503 Communication loss with Fan Board Number 3 As above Circuit C shuts down As above
66 4801 Communication loss with VLT Board Number 1,
(units w/o option 17)
As above Circuit A shuts down As above
67 4802 Communication loss with VLT Board Number 2,
(units w/o option 17)
As above Circuit B shuts down As above
68 4803 Communication loss with VLT Board Number 3,
(units w/o option 17)
As above Circuit C shuts down As above
69 4704 Loss of communication with Fan VLT Drive Board
A1 (option 17)
As above Circuit A shuts down As above
70 4705 Loss of communication with Fan VLT Drive Board
A2 (option 17)
As above Circuit A shuts down As above
71 4706 Loss of communication with Fan VLT Drive Board
A3 (option 17)
As above Circuit A shuts down As above
72 4707 Loss of communication with Fan VLT Drive Board
B1 (option 17)
As above Circuit B shuts down As above
73 4708 Loss of communication with Fan VLT Drive Board
B2 (option 17)
As above Circuit B shuts down As above
74 4709
Loss of communication with Fan VLT Drive Board
B3 (option 17)
As above Circuit B shuts down As above
PROCESS FAILURE
78 10001 Evaporator frost protection Manual Unit shuts down, but the pump
continues to run
No water ow,
defective thermistor
79
10002 Condenser frost protection, circuit A Automatic
(if saturated discharge
temperature is more
than 4.4°C) or Manual
Circuit A shuts down, but the pump
is running
Discharge pressure
transducer defective,
refrigerant leak or low
condenser water temperature
80
10003 Condenser frost protection, circuit B As above Circuit B shuts down, but the pump
is running
As above
81
10004 Condenser frost protection, circuit C As above Circuit C shuts down, but the pump
is running
As above
82
10005 Low suction temperature, circuit A Automatic (the rst
alarm in the last 24
hours) or Manual
Circuit A shuts down Pressure sensor defective,
EXV blocked or lack of
refrigerant
83
10006 Low suction temperature, circuit B As above Circuit B shuts down As above
84
10007 Low suction temperature, circuit C As above Circuit C shuts down As above
85
10008 High superheat, circuit A Manual Circuit A shuts down As above
86
10009 High superheat, circuit B Manual Circuit B shuts down As above
87
10010 High superheat, circuit C Manual Circuit C shuts down As above
88 10011 Low superheat, circuit A Manual Circuit A shuts down As above
89 10012 Low superheat, circuit B Manual Circuit B shuts down As above
90 10013 Low superheat, circuit C Manual Circuit C shuts down As above
91 10014 Customer safety loop failure Automatic (the rst
alarm in the last 24
hours) or Manual
Unit shuts down Customer interlock closed
92 10028 Electrical box thermostat Automatic Unit shuts down Electrical box fault: Control
box poorly ventilated or poor
electrical connection
93 10029 System manager communication fault Automatic, if
communication is
re-established
Unit returns to the stand-alone
mode
CCN bus installation
defective
94 10030 Master/slave communication failure Automatic Master/slave control disabled As above
110 10031 Emergency stop
Automatic Unit shuts down Network emergency stop
command
111 10032 Evaporator pump 1 fault Manual Unit is restarted with another pump
running. If no pumps are available,
the unit shuts down
Pump overheats or poor
pump connection
112 10033 Evaporator pump 2 fault Manual As above As above
113 10015 Flow controller fault - condenser ow switch failure Automatic (the rst
alarm in the last 24
hours) or Manual
Condenser pump is stopped Condenser ow switch open
114 10034 Reclaim operation failure, circuit A Manual Circuit A returns to the air-cooled
mode
Low condenser ow
115 10035 Reclaim operation failure, circuit B Manual Circuit B returns to the air-cooled
mode
As above
116 10037 High condensing temperature, circuit A Automatic Circuit A shuts down Defective transducer
117 10038 High condensing temperature, circuit B Automatic Circuit B shuts down As above
118 10039 High condensing temperature, circuit C Automatic Circuit C shuts down As above