25
Table 7 Standard Control Offerings
All control offerings provide the following features:
1. A 3-speed automatic fan control that minimizes fan noise by
matching the fan speed to the load. This process provides
better dehumidification during cooling and reduces energy
consumption.
2. American Society of Heating, Refrigeration and Air Conditioning
Engineers (ASHRAE) Cycle I, Cycle II, or Cycle III damper con-
trol options (Cycle II default).
3. Configurable minimum ventilation set point (cfm) for ASHRAE
Cycle II or Cycle III damper control.
4. Demand controlled ventilation with optional sensor to meet ven-
tilation requirements with improved efficiency.
5. Coil freeze protection on all units except non-water units.
6. Proportional Integrated Derivative (PID) logic heating, cooling
and damper controls to maintain temperature.
7. Adjustable filter maintenance timer on all units.
8. Direct shaft coupled, electric actuators on all dampers. Spring
return on outdoor-air (OA) damper.
9. Spring return modulating water valves.
10. Optional relative humidity sensor for high humidity control or
dehumidification.
11. Optional remote-mounted space sensor with set point adjust-
ment, tenant override, and service port jack.
12. Optional linkage thermostat with time clock, set point adjust-
ment, schedule and holiday programming, digital temperature,
set point and equipment status display.
LEGEND
Table 8 Field-Installed Accessories
Table 9 Factory-Installed Options
CONTROL SEQUENCE APPLICATION
Heating/Cooling Valve Control
2A/3A Chilled Water/Hot Water, 2-Pipe Changeover
2B/3B Chilled Water/Hot Water or Steam, 4-Pipe
2D/3D Chilled Water with Electric Heat
2F/3F Hot Water or Steam Heating Only
2G/3G Hot Water or Steam with DX Cooling
2J/3J Chilled Water Cooling Only
Heating/Cooling with Face and Bypass Damper Control
20/30 Chilled Water/Hot Water, 2-Pipe Changeover
21/31 Chilled Water/Hot Water or Steam, 4-Pipe
22/32 Chilled Water with Electric Heat
23/33 Hot Water or Steam with DX Cooling
24/34 Hot Water or Steam Heating Only
25/35 Chilled Water Cooling Only
Heating/Cooling with Humidity Control
2M/3M F&B Chilled Water/Hot Water or Steam Heating 4-Pipe plus Valve Control Reheat for
Dehumidification
2G/3G Cooling with Hot Water or Steam Reheat, Valve Control
2B/3B Chilled Water/Hot Water Reheat, 4-Pipe Valve Control
2K/3K F&B Chilled Water Cooling with Hot Water or Steam Valve Control Reheat, 4-Pipe
Non-Water Systems
OC Electric Heat Only
OE Electric Heat with DX Cooling
OH DX Cooling Only
DX Direct Expansion
F&B Face and Bypass
PACKAGE NO. PACKAGE DESCRIPTION
33CSKITLST-01 Programmable Linkage Thermostat with Timeclock
CGCDXSEN001A00 Wall-Mounted CO
2
Sensor (No Display)
CGCDXSEN002A00 Wall-Mounted CO
2
Sensor with Display
CGCDXGAS001A00 CO
2
Sensor Calibration Service Kit
HL39ZZ003 Wall-Mounted Relative Humidity Sensor
CODE DESCRIPTION
DIGIT #15 (2,S,M,4,V) Space Temperature Sensor
DIGIT #15 (1,0,R,3) Changeover Switch