ADDRESS SETTING
Non-Programmable Controller (40VM900002)
NOTE: You can only connect one wired controller to an indoor unit.
1. Press ROOM TEMP and SWING together for three seconds.
Fig. 39 —Non-Programmable Controller (40VM900002)
It displays FE# 00 if there is no address for this IDU. Otherwise, it displays the current address of the indoor unit.
2. Click TEMP.UP or TEMP.DOWN to change 00 to address number you want to set.
Programmable Controller (40VM900003)
NOTE: The address can only be set when the wired controller is connected to one indoor unit.
1. Press FAN and BACK simultaneously for five seconds to enter the interface for parameter settings.
Fig. 40 —Programmable Controller (40VM900003)
2. Press TEMP.UP or TEMP.DOWN to move the cursor down, and choose IDU ADDRESSING.
3. Select MENU/OK to enter this setting.
4. Press TEMP.UP or TEMP.DOWN to choose the address number you want to set.
5. Select MENU/OK to send this address to the IDU.
6. Press OK to confirm and exit the setting interface.
7. Press BACK twice, or wait 30 seconds to automatically exit the parameter settings menu.